Plan Review Notes
Plan Review Notes For Permit 19060842
Permit Number 19060842
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-20 15:12:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PALNS ARE TOO SMALL AND UNREADABLE AND
 THERE INSUFFICIENT DETAIL TO MAKE A DETEMINATION OF
 FIRE CODE COMPLIANCE.
  
 PLEASE PROVIDE LARGER READABLE PLANS AND PROVIDE
 GREATER DETAIL.
  
  
 2) DOES THIS BUIDLIGN HAVE FIRE SPRINKLERS AND FIRE
 ALARMS.
  
 PLEASE PROVIDE FS & FA DEVICE LOCATION AND PROVIDE AN
 APPLICABLE NOTE STATING ALL FS & FA WORK SHALL BE DONE
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 3) THERE IS INDICATIONS OF MOVING WASHER AND DRYER.
 PLEASE PROVIDE DRYER VENT DETAIL, INCLUDING VENT
 DIMENSIONS THAT MEET THE REQUIREMENTS OF THE DRYER
 MANUFACTURER.
  
 DRYER SPECIFICATIONS SHEETS NEED TO BE PROVDED TO
 ENSURE REQUIREMENTS ARE MET.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  