| Plan Review Notes For Permit 19060830 |
| Permit Number |
19060830 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-07-17 07:53:20 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. DESIGN PRESSURES SPECIFIED BY THE ENGINEER ARE | | | +85.4/-143.9; SEE PAGE 13, 60PSF WAS CIRCLED AND ANCHOR | | | SPACING FOR 60 PSF WAS SPECIFIED ON THE INSTALLATION | | | SCHEDULE. | | | | | | 3RD REVIEW, FASTENER NOT PERMITTED FOR 160PSF, 9' SPAN. | | | THE FASTENING FOR -60 PSF WAS CIRCLED, 4" SPECIFIED, | | | BUT THE COLUMN FOR -160PSF HAS A HYPHEN (-) IN THIS | | | BOX. | | | | | | 2. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | |
|