Plan Review Notes
Plan Review Notes For Permit 19060829
Permit Number 19060829
Review Stop B
Sequence Number 2
Notes
Date Text
2019-07-05 09:36:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DESIGN PRESSURES SPECIFIED BY THE ENGINEER ARE
 +83.5/-88.2; SEE PAGES 13 & 14, 60PSF WAS CIRCLED AND
 ANCHOR SPACING FOR 60 PSF WAS SPECIFIED ON THE
 INSTALLATION SCHEDULE.
  
 2. INSTALLATION SCHEDULE PROPOSES SHUTTER MOUNTING
 CONNECTION TYPES C AND F, BUT G AND I ARE CIRCLED.
  
 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  