Plan Review Notes
Plan Review Notes For Permit 19060814
Permit Number 19060814
Review Stop B
Sequence Number 2
Notes
Date Text
2019-06-27 17:53:41RE-ROOF RESIDENTIAL (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ACCORDING TO DBPR WEBSITE THE ROOFING CONTRACTOR'S
 LICENSE IS INACTIVE. CONTRACTOR CAN NOT DO WORK.
 CONTRACTOR NEEDS CURRENT/ACTIVE LICENSE. COORDINATE
 WITH DBPR.
 SEC. 489.116 FLORIDA STATUTE.
  
 CERTIFIED ROOFING CONTRACTOR WIKEL, DAVE LESLIE PRIMARY
 CCC1325862
 CERT ROOFING CURRENT, INACTIVE
  
 RESPONSE:
 CITY RECORDS STILL SHOWS LICENSE CCC1325862. CONTRACTOR
 TO COORDINATE WITH THE PERMIT CLERKS TO UPDATE LICENSE
 INFORMATION.
  
  
 ORIGINAL COMMENT:
 2- FLAT ROOF NOA 14-0627.05 SUBMITTED: SELECTED
 ASSEMBLY ON SHEET 7 OF 8 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. SEC. R301.2.1
 FBC-RESIDENTIAL. PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7.
  
 RESPONSE:
 A) CALCULATIONS SUBMITTED HAVE A COPY OF A DIGITAL
 SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL. DIGITAL
 SIGNATURES CAN NOT BE COPIED. SEE SEC. 61G15-23.004 FAC
 FOR PROCEDURES FOR DIGITALLY SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 THIS IS NOT A DIGITAL SUBMITTAL. ENGINEER NEEDS TO
 PROVIDE CALCULATIONS WITH ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 CERTIFIED ROOFING CONTRACTOR WIKEL, DAVE LESLIE PRIMARY
 CCC1325862
 CERT ROOFING CURRENT, INACTIVE
  