| Plan Review Notes For Permit 19060810 |
| Permit Number |
19060810 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-20 17:48:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1609, THE INSTALLATION SCHEDULE DOES NOT | | | SPECIFY WHICH TAPCON IS PROPOSED, PLEASE REVISE. PLEASE | | | NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON | | | SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF | | | USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON | | | W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). | | | | | | 3. FBC 107, THE PLAN SHOWS THE FRONT DOOR COVERED, AND | | | ANOTHER OPENING AS EGRESS. REVISE PLAN TO NOTE ROOM | | | DESIGNATION; THIS CANNOT BE A ROOM THAT IS NOT WITHIN | | | THE CONTROL OF THE OCCUPANT. | | | | | | |
|