Plan Review Notes
Plan Review Notes For Permit 19060808
Permit Number 19060808
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-07-19 13:51:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) REVIEW AND ENSURE COMPLIANCE WITH NFPA 13; 6.9.1
  
 6.9 WATERFLOW ALARM DEVICES.
 6.9.1 GENERAL. WATERFLOW ALARM DEVICES SHALL BE LISTED
 FOR THE
 SERVICE AND SO CONSTRUCTED AND INSTALLED THAT ANY FLOW
 OF WATER
 FROM A SPRINKLER SYSTEM EQUAL TO OR GREATER THAN THAT
 FROM A
 SINGLE AUTOMATIC SPRINKLER OF THE SMALLEST K-FACTOR
 INSTALLED ON
 THE SYSTEM WILL RESULT IN AN AUDIBLE ALARM ON THE
 PREMISES WITHIN
 5 MINUTES AFTER SUCH FLOW BEGINS AND UNTIL SUCH FLOW
 STOPS.
  
  
 2) PROVIDE MANUFACTURES SPECIFICATION SHEETS FOR THE
 FIRE INSPECTOR REVIEW ON FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  