| Plan Review Notes For Permit 19060808 |
| Permit Number |
19060808 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-07-19 13:51:49 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) REVIEW AND ENSURE COMPLIANCE WITH NFPA 13; 6.9.1 | | | | | | 6.9 WATERFLOW ALARM DEVICES. | | | 6.9.1 GENERAL. WATERFLOW ALARM DEVICES SHALL BE LISTED | | | FOR THE | | | SERVICE AND SO CONSTRUCTED AND INSTALLED THAT ANY FLOW | | | OF WATER | | | FROM A SPRINKLER SYSTEM EQUAL TO OR GREATER THAN THAT | | | FROM A | | | SINGLE AUTOMATIC SPRINKLER OF THE SMALLEST K-FACTOR | | | INSTALLED ON | | | THE SYSTEM WILL RESULT IN AN AUDIBLE ALARM ON THE | | | PREMISES WITHIN | | | 5 MINUTES AFTER SUCH FLOW BEGINS AND UNTIL SUCH FLOW | | | STOPS. | | | | | | | | | 2) PROVIDE MANUFACTURES SPECIFICATION SHEETS FOR THE | | | FIRE INSPECTOR REVIEW ON FIRE INSPECTIONS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|