| 2019-07-12 16:21:49 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19060806 |
| | REVIEWED: JULY 12, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH |
| | CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN |
| | ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL |
| | COST OF WORK. PLEASE ADJUST FEE AT FRONT DESK AND PAY |
| | ADJUSTED PERMIT REVIEW FEE AT TIME OF RE-SUBMITTAL. |
| | - ALSO, PROVIDE PROJECT DESCRIPTION IF IT IS NOT |
| | INCLUDED ON THE PROPOSAL. |
| | |
| | 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| | SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| | A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE |
| | METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| | OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN |
| | BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| | CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE |
| | SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| | OF THIS CODE. |
| | C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF |
| | THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | - WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| | (PRESCRIPTIVE,WORK AREA OR PERFORMANCE). |
| | |
| | 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED IF WORK AREA COMPLIANCE METHOD IS |
| | BEING USED. |
| | |
| | 107.5.3 FBC[AMENDED] PLEASE PROVIDE DRAWING THAT DEPICT |
| | EXISTING CONDITIONS, DEMOLITION (IF APPLICABLE) AND |
| | PROPOSED CHANGES. DESIGN CRITERIA, PRODUCT APPROVALS, |
| | SCHEDULES AND DETAILS FOR NEW WORK. |
| | NEW WORK WILL NEED TO COMPLY WITH ENERGY CODE. |
| | ALSO, THE FLOOR PLAN LABELED AS-BUILT SOUNDS LIKE WORK |
| | HAS BEEN PERFORMED. IS THIS WORK ALREADY COMPLETE? |
| | |
| | REVIEW HAS NOT BEEN PERFORMED DUE TO LACK OF |
| | INFORMATION ON THE PLANS. PLEASE PROVIDE TWO SETS OF |
| | PLANS THAT DEPICT THE WORK TO BE PERFORMED SO THAT A |
| | REVIEW CAN BE COMPLETED ON THE SECOND REVIEW. |
| | |
| | NOTES: |
| | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| | REQUIRED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |