| 2019-06-25 14:11:19 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | PLEASE NOTE THAT SOME ISSUES ARE ARCHITECTURAL. THESE |
| | ISSUES MUST BE SATISFACTORILY ADDRESSED PRIOR TO |
| | APPROVAL OF THE PLUMBING APPLICATION FOR PERMIT. |
| | 1. RE: PLAN SHEET AS101; |
| | A. BUILDING CODE ANALYSIS INDICATES USE & OCCUPANCY IS |
| | MERCANTILE AND STORAGE. PER WPB FBC 107.2.1, THE |
| | ARCHITECT SHALL PROVIDE THE OCCUPANT LOAD FOR THE |
| | BUILDING IN ACCORDANCE WITH FBC 1004.1. |
| | 1) AS I SEE IT THE OCCUPANT LOAD FOR THE BUILDING |
| | EXCEEDS 15 PERSONS WHICH WILL REQUIRE A DRINKING |
| | FOUNTAIN AND A SERVICE SINK PER FBC PL TABLE 403.1. |
| | 2. RE: PLAN SHEET AE106; |
| | A. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36 |
| | INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE, NOT TO CENTER OF |
| | THE GRIPPING SURFACE. |
| | B. PER WPB FBC 107.2.1, PLEASE REMOVE ALL DETAILS THAT |
| | DO NOT PERTAIN TO THE PROJECT. THIS INCLUDES, BUT IS |
| | NOT LIMITED TO DETAILS FOR THE SHOWER, FLOOR MOP SINK |
| | AND THE URINAL. |
| | 3. RE: PLAN SHEET AE101; |
| | A. RM. 102: PER FBC ACC 212.3, WHERE SINKS ARE |
| | PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF |
| | EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE |
| | SHALL COMPLY WITH 606. (PLEASE NOTE, MOP OR SERVICE |
| | SINKS SHALL NOT BE REQUIRED TO COMPLY WITH 212.3.) |
| | B. PER FBC ACC SECTION 606.2, PROVIDE CLEAR FLOOR SPACE |
| | FOR THE SINK. |
| | C.PER FBC ACC 606.3, SINK SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | 4. RE: PLAN SHEET P-1; |
| | A. THE WATER HEATER SCHEDULE CALLS FOR AN EEMAX |
| | TANKLESS ELECTRIC WATER HEATER; THE WATER HEATER DETAIL |
| | SHOWS THE WATER HEATER TO BE A TANK TYPE WITH STORAGE. |
| | ADDITIONALLY, THERE IS AN IN-LINE HI-LO THERMOSTATIC |
| | MIXING VALVE SHOWN. PER WPB FBC 107.2.1, PLEASE |
| | CLARIFY. IF THE WATER HEATER DETAIL SHOWN ON THE PLAN |
| | DOES NOT APPLY, THEN PLEASE REMOVE IT PER WPB FBC |
| | 107.2.1. |
| | B. PER WPB FBC 107.2.1, PROVIDE THE ELECTRICAL |
| | CHARACTERISTICS OF THE WATER HEATER ON THE SCHEDULE. |
| | C. P & T RELIEF VALVE IS CALLED OUT ON THE SCHEDULE. IS |
| | THIS REQUIRED ON A TANKLESS WATER HEATER. IF IT IS, |
| | THEN PER WPB FBC 107.2.1, PROVIDE A DETAIL OF THE UNIT, |
| | WITH PIPING AND VALVE ARRANGEMENT, INCLUDING LOCATION |
| | OF THE RELIEF VALVE AND DISCHARGE PIPING. |
| | D. SEE PLUMBING FIXTURE SCHEDULE. PER FBC PL 416.5, |
| | PROVIDE TEMPERING WATER DEVICE AT THE LAVATORIES |
| | CONFORMING TO ASSE 1070 OR CSA B125.3. |
| | E.PER FBC TABLE 403.1, PROVIDE A DRINKING FOUNTAIN AND |
| | SERVICE SINK. |
| | 1) PER FBC PL 410.3, REQUIRED DRINKING FOUNTAIN SHALL |
| | BE A BI-LEVEL WITH TWO SPOUTS WHICH ACCOMMODATES WHEEL |
| | CHAIR ACCESSIBILITY AND MEETS THE NEEDS OF STANDING |
| | PEOPLE, OR TWO SEPARATE DRINKING FOUNTAINS MEETING |
| | THOSE SAME REQUIREMENTS SHALL BE FURNISHED. |
| | 5. PLUMBING SHEETS SIGNATURE IS BY ENGINEER AND IS |
| | SELF-CERTIFIED; REQUIRES THIRD PARTY CERTIFICATION. |
| | ADDITIONALLY, THERE IS A NOTE ON EACH OF THE PLUMBING |
| | PLANS STATING THAT THE PLAN HAS BEEN ELECTRONICALLY |
| | SIGNED AND SEALED BY JASON D. P.E. 73050 USING A SHA-1 |
| | AUTHENTICATION CODE. IS THIS A LEGITIMATE CERTIFIED |
| | AUTHORITY? PLEAS PROVIDE TRUSTED CERTIFICATE AUTHORITY. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19060803 8225 IBIS BLVD |
| | |