| 2019-07-09 12:14:04 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19060803 |
| | 7/9/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTIONS |
| | C101.2, C101.5.1 AND C401.2 FBC EC. |
| | |
| | 3) SHEETS AE101 & M-3: THE "FITTING ROOM" APPEARS TO BE |
| | AN OCCUPIED SPACE THAT REQUIRES EITHER NATURAL OR |
| | MECHANICAL VENTILATION, AND A SPACE HEATING SYSTEM. |
| | PLEASE SEE SECTIONS 401.2 & 309.1 FBC M AND SHOW |
| | COMPLIANCE. |
| | |
| | 4) AE101 & M-3: "FITTING ROOMS" PER TABLE 403.3.1.1 FBC |
| | REQUIRE EXHAUST VENTILATION AT A RATE OF 0.25 CFMS PER |
| | SQ. FT. THERE IS ALSO A LARGE OVERHEAD ROLL-UP DOOR |
| | THAT WOULD ALLOW VEHICLES TO ACCESS THE SPACE AND BE |
| | STORED THERE. PLEASE NOTE THAT EXHAUST VENTILATION AT A |
| | RATE OF 0.75 CFMS PER SQ. FT. IS REQUIRED FOR GARAGES- |
| | TABLE 403.3.1.1 FBC M. PLEASE REVISE THE PLANS TO MEET |
| | COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |