| 2019-06-24 09:56:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) A WATER SUPPLY/FIRE HYDRANT COULD NOT BE IDENTIFIED |
| | NEAR OF AROUND THE PROPOSED BUILDING. |
| | |
| | A WATER SUPPLY IS REQUIRED. |
| | |
| | PER NFPA 1 |
| | |
| | 18.3 WATER SUPPLIES. |
| | 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING |
| | THE REQUIRED |
| | FIRE FLOW FOR FIRE PROTECTION SHALL BE PROVIDED TO ALL |
| | PREMISES UPON |
| | WHICH FACILITIES, BUILDINGS, OR PORTIONS OF BUILDINGS |
| | ARE HEREAFTER |
| | CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE |
| | APPROVED WATER |
| | SUPPLY SHALL BE IN ACCORDANCE WITH SECTION 18.4. |
| | |
| | 18.4.5.3 BUILDINGS OTHER THAN ONE- AND TWO-FAMILY |
| | DWELLINGS. |
| | 18.4.5.3.1 THE MINIMUM FIRE FLOW AND FLOW DURATION FOR |
| | BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS |
| | SHALL BE AS |
| | SPECIFIED IN TABLE 18.4.5.2.1. |
| | |
| | 18.5 FIRE HYDRANTS. |
| | 18.5.1 FIRE HYDRANT LOCATIONS AND DISTRIBUTION. FIRE |
| | HYDRANTS |
| | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 18.5 FOR |
| | ALL NEW |
| | BUILDINGS, OR BUILDINGS RELOCATED INTO THE JURISDICTION |
| | UNLESS OTHERWISE |
| | PERMITTED BY 18.5.1.1 OR 18.5.1.2. |
| | |
| | 18.5.3 BUILDINGS OTHER THAN DETACHED ONE- AND |
| | TWO-FAMILY |
| | DWELLINGS. FIRE HYDRANTS SHALL BE PROVIDED FOR |
| | BUILDINGS OTHER |
| | THAN DETACHED ONE- AND TWO-FAMILY DWELLINGS IN |
| | ACCORDANCE WITH |
| | BOTH OF THE FOLLOWING: |
| | (1) THE MAXIMUM DISTANCE TO A FIRE HYDRANT FROM THE |
| | CLOSEST |
| | POINT ON THE BUILDING SHALL NOT EXCEED 400 FT (122 M). |
| | (2) THE MAXIMUM DISTANCE BETWEEN FIRE HYDRANTS SHALL |
| | NOT |
| | EXCEED 500 FT (152 M). |
| | |
| | PLEASE INDICATE WHERE THE CLOSET FIRE HYDRANT IS OR |
| | PROVIDE ONE THAT MEETS THE ABOVE NOTED CODES. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |