| Plan Review Notes For Permit 19060771 |
| Permit Number |
19060771 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-20 17:25:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC R 301 | | | | | | 1. TWO NUMBERS ARE SPECIFIED FOR THE TOP MOUNT; ONLY | | | ONE SHOULD BE SPECIFIED, REVISE ACCORDINGLY. | | | | | | 2. SEE PAGE 13, ITW TAPCON IS NOT ONE SPECIFIED; REVISE | | | TO BE CONSISTENT WITH THE FASTENERS IN THE PRODUCT | | | APPROVAL. | | | | | | 3. EDGE DISTANCE FOR WALL HEADER B IS SPECIFIED AS | | | 1.75; SEE THE EDGE DISTANCE CHART ON PAGE 13; A FACTOR | | | APPLIES. THE FACTOR DEPENDS ON THE FASTENER, WHICH IS | | | NOT CLEAR. | | | | | | PLEASE CALL ME IF YOU WISH TO DISCUSS. | | | | | | |
|