| 2019-08-13 07:22:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. AS PER LAST PLAN REVIEW COMMENTS NO LOAD CALCULATION |
| | HAS BEEN PROVIDED SHOWING EDITION THE EXISTING LOAD AND |
| | THE ADDITION OF NEW RECEPTACLES TO PANEL "LA". LOAD |
| | CALCULATION PROVIDED APPEARS TO BE A RESIDENTIAL LOAD |
| | CALC FOR A UNIT AND A 200AMP SERVICE AT 220V??? PROVIDE |
| | CORRECTION. FBC 107.2.1 NEC 220. |
| | |
| | 2. AS PER LAST PLAN REVIEW COMMENTS PLAN IS NOT SIGNED |
| | BY ELECTRICAL CONTACTOR QUALIFIER. (EVERY PAGE) . |
| | PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC |
| | 107.1 |
| | |
| | 3. AS PER LAST PLAN REVIEW COMMENTS NOTHING WAS |
| | ADDRESSED IN RELATION TO DERATING CONDUCTORS. 1-1/2'' |
| | CONDUITS SHOWS 12 CURRENT CARRYING CONDUCTORS, AFTER |
| | DERATING AT 50% #6 WIRE IS RATED AT 37.5 AMPS AND MAX |
| | OCP ALLOWED WOULD BE 40 AMPS PER NEC 240.4B. SPECS |
| | SHEET PROVIDED CALLS FOR MINIMUM CIRCUIT AMPACITY OF |
| | 40AMP AND OCP OF 50AMPS. PROVIDE CORRECTION. |
| | |
| | 4. PROVIDE SPEC SHEETS FOR PRODUCT APPROVAL SHOWING UL |
| | LISTING OR OTHER NRTL LISTING. FBC 107.2.1 NEC |
| | 90.7,110.2,110.3B |
| | |
| | 5. SHOW COMPLIANCE FOR ADA IN REFERENCE TO CAR CHARGERS |
| | AND LOCATIONS. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |