Plan Review Notes
Plan Review Notes For Permit 19060746
Permit Number 19060746
Review Stop E
Sequence Number 2
Notes
Date Text
2019-08-13 07:22:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AS PER LAST PLAN REVIEW COMMENTS NO LOAD CALCULATION
 HAS BEEN PROVIDED SHOWING EDITION THE EXISTING LOAD AND
 THE ADDITION OF NEW RECEPTACLES TO PANEL "LA". LOAD
 CALCULATION PROVIDED APPEARS TO BE A RESIDENTIAL LOAD
 CALC FOR A UNIT AND A 200AMP SERVICE AT 220V??? PROVIDE
 CORRECTION. FBC 107.2.1 NEC 220.
  
 2. AS PER LAST PLAN REVIEW COMMENTS PLAN IS NOT SIGNED
 BY ELECTRICAL CONTACTOR QUALIFIER. (EVERY PAGE) .
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC
 107.1
  
 3. AS PER LAST PLAN REVIEW COMMENTS NOTHING WAS
 ADDRESSED IN RELATION TO DERATING CONDUCTORS. 1-1/2''
 CONDUITS SHOWS 12 CURRENT CARRYING CONDUCTORS, AFTER
 DERATING AT 50% #6 WIRE IS RATED AT 37.5 AMPS AND MAX
 OCP ALLOWED WOULD BE 40 AMPS PER NEC 240.4B. SPECS
 SHEET PROVIDED CALLS FOR MINIMUM CIRCUIT AMPACITY OF
 40AMP AND OCP OF 50AMPS. PROVIDE CORRECTION.
  
 4. PROVIDE SPEC SHEETS FOR PRODUCT APPROVAL SHOWING UL
 LISTING OR OTHER NRTL LISTING. FBC 107.2.1 NEC
 90.7,110.2,110.3B
  
 5. SHOW COMPLIANCE FOR ADA IN REFERENCE TO CAR CHARGERS
 AND LOCATIONS.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  