| 2019-06-25 06:53:58 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOT ENOUGH INFORMATION ON PLAN. PLEASE PROVIDE PLAN |
| | INCLUDING GARAGE LAYOUT AND ACTUAL LOCATION OF NEW |
| | JBOXES, NEW RECEPTACLES, AND ELEC ROOM. FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED |
| | WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED (EVERY |
| | PAGE) BY THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE |
| | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 3. IS PANEL 3 PHASE? WHAT IS VOLTAGE OF PANEL? LOAD |
| | CALC IS DIVDED BY 220 FOR VOLTAGE. VOLTAGE IS BELIEVED |
| | TO BE 208. NEC 220, FBC 107.2.1 |
| | |
| | 4. PROVIDE ACCURATE LOAD CALCULATION PROVIDING ALL |
| | LOADS BOTH NEW AND EXISTING. NEW RECEPTACLES LOADS ARE |
| | NOT SHOWN IN LOAD CALCULATION. |
| | |
| | 5. ARE NEW RECEPTACLES FOR CAR CHARGERS? PLEASE PROVIDE |
| | MORE INFORMATION. FBC 107.2.1 |
| | |
| | 6. 8, #6'S AND 4, #8 CONDUCTORS SHOWN IN ONE 1-1/2 |
| | CONDUIT. TOTAL OF 12 CURRENT-CARRYING-CONDUCTORS. AFTER |
| | ADJUSTMENT FACTORS ARE APPLIED PER NEC 310.15B3A THE |
| | CONDUCTORS ARE NOT SUFFICENT FOR A 50AMP OCP PROTECTED |
| | CIRCUIT. YOU MUST DERATE CONDUCTORS @ 50% @ 90 DEGREES |
| | CELCIUS |
| | |
| | #6 @ 90 DEGREES IS RATED AT 75A. 75X50%= 37.5AMPS. |
| | CONDUCTOR RATING MUST MATCH OCP RATING PER NEC 210.3. |
| | |
| | #8 @ 90 DEGREES IS RATED AT 55A. 55X50%= 22.5AMPS. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |
| | |