Plan Review Notes
Plan Review Notes For Permit 19060746
Permit Number 19060746
Review Stop E
Sequence Number 1
Notes
Date Text
2019-06-25 06:53:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOT ENOUGH INFORMATION ON PLAN. PLEASE PROVIDE PLAN
 INCLUDING GARAGE LAYOUT AND ACTUAL LOCATION OF NEW
 JBOXES, NEW RECEPTACLES, AND ELEC ROOM. FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED (EVERY
 PAGE) BY THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 3. IS PANEL 3 PHASE? WHAT IS VOLTAGE OF PANEL? LOAD
 CALC IS DIVDED BY 220 FOR VOLTAGE. VOLTAGE IS BELIEVED
 TO BE 208. NEC 220, FBC 107.2.1
  
 4. PROVIDE ACCURATE LOAD CALCULATION PROVIDING ALL
 LOADS BOTH NEW AND EXISTING. NEW RECEPTACLES LOADS ARE
 NOT SHOWN IN LOAD CALCULATION.
  
 5. ARE NEW RECEPTACLES FOR CAR CHARGERS? PLEASE PROVIDE
 MORE INFORMATION. FBC 107.2.1
  
 6. 8, #6'S AND 4, #8 CONDUCTORS SHOWN IN ONE 1-1/2
 CONDUIT. TOTAL OF 12 CURRENT-CARRYING-CONDUCTORS. AFTER
 ADJUSTMENT FACTORS ARE APPLIED PER NEC 310.15B3A THE
 CONDUCTORS ARE NOT SUFFICENT FOR A 50AMP OCP PROTECTED
 CIRCUIT. YOU MUST DERATE CONDUCTORS @ 50% @ 90 DEGREES
 CELCIUS
  
 #6 @ 90 DEGREES IS RATED AT 75A. 75X50%= 37.5AMPS.
 CONDUCTOR RATING MUST MATCH OCP RATING PER NEC 210.3.
  
 #8 @ 90 DEGREES IS RATED AT 55A. 55X50%= 22.5AMPS.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH