| Date |
Text |
| 2019-06-24 16:17:30 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19060712 |
| | REVIEWED: JUNE 24, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 301.2.1.1 FBC[R] WIND DESIGN CRITERIA |
| | RISK CATEGORY = ___(II) |
| | EXPOSURE CATEGORY = ___(B,C OR D) |
| | BUILDING CLASSIFICATION = __________(ENCLOSED) |
| | MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT |
| | MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF |
| | PEAK) |
| | WIND SPEED V ULT = _____(170) |
| | WIND SPEED V ASD = _____(132) |
| | -PLEASE ADD WIND DESIGN CRITERIA TO COVER SHEET. |
| | |
| | 2) PLEASE PROVIDE ON ADDITIONAL COPY OF EACH PRODUCT |
| | APPROVAL. EACH PERMIT NEEDS 2 SETS OF PRODUCT APPROVALS |
| | AND BETWEEN THE TWO PERMITS I WAS ONLY ABLE TO FIND |
| | ENOUGH FOR ONE SET EACH. |
| | 17-0630.01, 17-0411.06, 17-0614.11 AND FL-15210.1 |
| | |
| | 3) THE WINDOW MARKS ON SHEET A1 AND A2 DON?T MATCH THE |
| | MARKS ON COVER. -PLEASE SHOW MARKS ON COVER TO MATCH SO |
| | ONLY COVER GETS REVISED. |
| | ALSO, MARK EGRESS ON HORIZONTAL SLIDER IF THAT IS |
| | INTENDED FOR BEDROOM EMERGENCY ESCAPE. |
| | |
| | 4) 310.1 FBC[R] UNITS 409W AND 409E HAVE NO EMERGENCY |
| | ESCAPE AND NO OPERABLE WINDOWS. THIS IS TECHNICALLY A |
| | SLEEPING ROOM AND SHOULD HAVE A WINDOW FOR EMERGENCY |
| | EGRESS. ALSO, THERE WOULD BE NO NATURAL VENTILATION |
| | PROVIDED. |
| | |
| | 5) R303.3 BATHROOMS. BATHROOMS, WATER CLOSET |
| | COMPARTMENTS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED |
| | WITH AGGREGATE GLAZING AREA IN WINDOWS OF NOT LESS THAN |
| | 3 SQUARE FEET (0.3 M2), ONE-HALF OF WHICH MUST BE |
| | OPENABLE. |
| | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE |
| | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE |
| | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE |
| | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST |
| | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE |
| | OUTDOORS |
| | HOW ARE BATHROOMS (ALL UNITS) VENTILATED? |
| | -SHOW MECHANICAL VENTILATION IF FIXED WINDOWS ARE BEING |
| | USED. |
| | |
| | NOTES: |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |