Plan Review Notes
Plan Review Notes For Permit 19060707
Permit Number 19060707
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-01 14:54:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060707
 ADD: 5600 N. FLAGLER DR. SUITE: 2605
 CONT: SUNSET VIEW CONSTRUCTION
 TEL: 561-289-6737
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 01/2019
 ACTION: DENIED
  
 1) SHEET A1:
  
 1A) CODE REFERENCES, TYPE OF CONSTRUCTION AS I. I-A OR
 I-B? ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) CODE REFERENCES, INDICATES THE OCCUPANCY TYPE AS
 R-3. R-3 IS ONE AND TWO FAMILY DWELLINGS. SEE 2017
 FBC-B 310.5. A CONDOMINIUM (APARTMENT HOUSE) IS
 OCCUPANCY TYPE R-2 SEE SECTION 310.4.
  
 1C) THE COVERSHEET A1 DOES NOT INDICATE IF THE BUILDING
 IS FIRE SPRINKLERED OR NOT? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
 1D) KEY NOTE FLOOR PLAN # 22INDICATES A 1-HOUR FIRE
 RATED WALL, UL-U-465, BUT THE WALL IDENTIFICATION TAG
 FOR NOTE 22 IS NOT FOUND ON THE FLOOR PLAN? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1E) THE DEMOLITION PLAN SHOWS THE ENTRY DOOR AND WATER
 HEATER CLOSET DOORS BEING REPLACED. ON THE PROPOSED
 FLOOR PLAN THE FRONT ENTRY DOOR IS NOT ADDRESSED. IN
 THE 2017 FBC-B TABLE 1020.1 WHEN SPRINKLERED THE FIRE
 RATING IS ? HOUR, OPENING PROTECTIVE 20 MIN. SEE TABLE
 716.5.
  
 1F) THE DOOR SCHEDULE, DOOR # 1 IS FOR THE HOT WATER
 HEATER, CLOTHES WASHER & DRYER CLOSET. THE DOOR
 SCHEDULE UNDER REMARKS INDICATES ADD PANIC HARDWARE?
 DOORS 3 & 9 ALSO INDICATE PANIC HARDWARE? TYPO?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) SHEET A-1 THE COVERSHEET NOTES 19 AND 20 INDICATE
 TO REPLACE THE SLIDING GLASS DOORS AND JAMBS, NOTE 20
 TO REPLACE THE EXISTING WINDOW AND FRAME. SHEET A-2
 INDICATES THE POSITIVE AND NEGATIVE PRESSURES FOR THE 3
 DOOR AND WINDOW UNITS SHOWN. WHAT THE PLAN DOES NOT
 PROVIDE IS THE EXPOSURE AND IN WHAT FORM THE PRESSURES
 ARE GIVEN, VULT OR VASD.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. EXPOSURE?
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 2B) DOOR AND WINDOW SCHEDULE, UNIT TYPE C INDICATES THE
 SAME PRODUCT APPROVAL NUMBER AS THE SLIDING GLASS
 DOORS, FL. 1909.2.1. DISCREPANCY IN PLANS. 107.2.1.2.
  
 2C)(1) THE PLAN DOES INDICATE THE PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOORS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING A, B, C OR D, LARGE
 MISSILE OR NOT, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. PLEASE ALSO
 IDENTIFY THE TYPE OF RISER TO BE INSTALLED FOR THE
 BOTTOM TRACK THIS WILL BE THE LIMITING FACTOR FOR
 PRESSURES IN SOME CASES. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 2C)(2) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS & MULLIONS
  
 2D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  