Plan Review Notes
Plan Review Notes For Permit 19060706
Permit Number 19060706
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-25 12:31:19PLUMBING1ST REVIEW**DENIED**
  
 1) PROVIDE SHOWER DETAIL SHOWING IT MEETS THE MIN
 REQUIREMENT. SEE BELOW.FBCR-P2708.1
 SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900 SQUARE
 INCHES (0.6 M2) OF INTERIOR CROSS-SECTIONAL AREA.
 SHOWER COMPARTMENTS SHALL BE NOT LESS THAN 30 INCHES
 (762 MM) IN MINIMUM DIMENSION MEASURED FROM THE
 FINISHED INTERIOR DIMENSION OF THE SHOWER COMPARTMENT,
 EXCLUSIVE OF FIXTURE VALVES, SHOWER HEADS, SOAP DISHES,
 AND SAFETY GRAB BARS OR RAILS. THE MINIMUM REQUIRED
 AREA AND DIMENSION SHALL BE MEASURED FROM THE FINISHED
 INTERIOR DIMENSION AT A HEIGHT EQUAL TO THE TOP OF THE
 THRESHOLD AND AT A POINT TANGENT TO ITS CENTERLINE AND
 SHALL BE CONTINUED TO A HEIGHT OF NOT LESS THAN 70
 INCHES (1778 MM) ABOVE THE SHOWER DRAIN OUTLET. HINGED
 SHOWER DOORS SHALL OPEN OUTWARD. THE WALL AREA ABOVE
 BUILTIN TUBS HAVING INSTALLED SHOWER HEADS AND IN
 SHOWER COMPARTMENTS SHALL BE CONSTRUCTED IN ACCORDANCE
 WITH SECTION R702.4. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB, RECEPTOR OR SHOWER FLOOR.
  
 EXCEPTIONS:
  
 1.FOLD-DOWN SEATS SHALL BE PERMITTED IN THE SHOWER,
 PROVIDED THE REQUIRED 900-SQUARE-INCH (0.6 M2)
 DIMENSION IS MAINTAINED WHEN THE SEAT IS IN THE
 FOLDED-UP POSITION.
 2.SHOWER COMPARTMENTS HAVING NOT LESS THAN 25 INCHES
 (635 MM) IN MINIMUM DIMENSION MEASURED FROM THE
 FINISHED INTERIOR DIMENSION OF THE COMPARTMENT PROVIDED
 THAT THE SHOWER COMPARTMENT HAS A CROSS-SECTIONAL AREA
 OF NOT LESS THAN 1,300 SQUARE INCHES (0.838 M2).
  
 2) PROVIDE BATHROOM DIMENSIONS. FBC 107.3.5P2708.1.1.
 ACCESS.THE SHOWER COMPARTMENT ACCESS AND EGRESS OPENING
 SHALL HAVE A CLEAR AND UNOBSTRUCTED FINISHED WIDTH OF
 NOT LESS THAN 22 INCHES (559 MM).
  
 3) PLUMBING ISOMETRIC DOES NOT MATCH FLOOR PLAN.
 ISOMETRIC SHOW DOUBLE LAV AND WITH A TUB AND A HALF
 BATHROOM. PLEASE CLARIFY. FBC 107.2.1
  
 4) PROVIDE LOCATION OF WATER HEATER ON FLOOR PLAN. FBC
 107.2.1
  
 5) STORAGE WATER HEATER DETAIL ON SHT. P1 IS MISSING
 THE PAN DRAIN LINE TO THE OUTSIDE. SHT.E1 IS CALLING
 OUT FOR A TANKLESS. PLEASE CLARIFY AND PROVIDE
 INSTALLATION MANUAL FOR THE UNIT YOUR INTENT TO USE.
 FBCR-P2801.6.2
  
 6) PLANS ARE REQUIRED TO BE SIGNED BY PERSON OF DESIGN.
 FS 471, 481, 489
  
 7) VALUE APPEARS LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT. WPB AMEND 109.3
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR