| 2019-06-25 12:31:19 | PLUMBING1ST REVIEW**DENIED** |
| | |
| | 1) PROVIDE SHOWER DETAIL SHOWING IT MEETS THE MIN |
| | REQUIREMENT. SEE BELOW.FBCR-P2708.1 |
| | SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900 SQUARE |
| | INCHES (0.6 M2) OF INTERIOR CROSS-SECTIONAL AREA. |
| | SHOWER COMPARTMENTS SHALL BE NOT LESS THAN 30 INCHES |
| | (762 MM) IN MINIMUM DIMENSION MEASURED FROM THE |
| | FINISHED INTERIOR DIMENSION OF THE SHOWER COMPARTMENT, |
| | EXCLUSIVE OF FIXTURE VALVES, SHOWER HEADS, SOAP DISHES, |
| | AND SAFETY GRAB BARS OR RAILS. THE MINIMUM REQUIRED |
| | AREA AND DIMENSION SHALL BE MEASURED FROM THE FINISHED |
| | INTERIOR DIMENSION AT A HEIGHT EQUAL TO THE TOP OF THE |
| | THRESHOLD AND AT A POINT TANGENT TO ITS CENTERLINE AND |
| | SHALL BE CONTINUED TO A HEIGHT OF NOT LESS THAN 70 |
| | INCHES (1778 MM) ABOVE THE SHOWER DRAIN OUTLET. HINGED |
| | SHOWER DOORS SHALL OPEN OUTWARD. THE WALL AREA ABOVE |
| | BUILTIN TUBS HAVING INSTALLED SHOWER HEADS AND IN |
| | SHOWER COMPARTMENTS SHALL BE CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION R702.4. SUCH WALLS SHALL FORM A |
| | WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE |
| | TUB, RECEPTOR OR SHOWER FLOOR. |
| | |
| | EXCEPTIONS: |
| | |
| | 1.FOLD-DOWN SEATS SHALL BE PERMITTED IN THE SHOWER, |
| | PROVIDED THE REQUIRED 900-SQUARE-INCH (0.6 M2) |
| | DIMENSION IS MAINTAINED WHEN THE SEAT IS IN THE |
| | FOLDED-UP POSITION. |
| | 2.SHOWER COMPARTMENTS HAVING NOT LESS THAN 25 INCHES |
| | (635 MM) IN MINIMUM DIMENSION MEASURED FROM THE |
| | FINISHED INTERIOR DIMENSION OF THE COMPARTMENT PROVIDED |
| | THAT THE SHOWER COMPARTMENT HAS A CROSS-SECTIONAL AREA |
| | OF NOT LESS THAN 1,300 SQUARE INCHES (0.838 M2). |
| | |
| | 2) PROVIDE BATHROOM DIMENSIONS. FBC 107.3.5P2708.1.1. |
| | ACCESS.THE SHOWER COMPARTMENT ACCESS AND EGRESS OPENING |
| | SHALL HAVE A CLEAR AND UNOBSTRUCTED FINISHED WIDTH OF |
| | NOT LESS THAN 22 INCHES (559 MM). |
| | |
| | 3) PLUMBING ISOMETRIC DOES NOT MATCH FLOOR PLAN. |
| | ISOMETRIC SHOW DOUBLE LAV AND WITH A TUB AND A HALF |
| | BATHROOM. PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 4) PROVIDE LOCATION OF WATER HEATER ON FLOOR PLAN. FBC |
| | 107.2.1 |
| | |
| | 5) STORAGE WATER HEATER DETAIL ON SHT. P1 IS MISSING |
| | THE PAN DRAIN LINE TO THE OUTSIDE. SHT.E1 IS CALLING |
| | OUT FOR A TANKLESS. PLEASE CLARIFY AND PROVIDE |
| | INSTALLATION MANUAL FOR THE UNIT YOUR INTENT TO USE. |
| | FBCR-P2801.6.2 |
| | |
| | 6) PLANS ARE REQUIRED TO BE SIGNED BY PERSON OF DESIGN. |
| | FS 471, 481, 489 |
| | |
| | 7) VALUE APPEARS LOW. PROVIDE A SIGNED BONA FIDE |
| | CONTRACT. WPB AMEND 109.3 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |