2019-07-22 12:34:46BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19060706
 REVIEWED: JULY 22, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED] 107.2.1FBC[AMENDED] ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 -PLEASE ADD SIGNATURE OF RESPONSIBLE PARTY.
  
 2) 501 FBC[EXISTING] LEVEL OF ALTERATION FOR WORK BEING
 PERFORMED.
 - THIS IS A NEW STRUCTURE AND NOT LEVEL II ALTERATION.
 PLEASE ADD OCCUPANCY CLASSIFICATION R-3.
  
 3) WAS THE ADDITION WORK COMPLETED FROM PERMIT
 02111028? DESCRIPTION SAYS ADDTION CONSISTING OF 2
 BEDROOMS CLOET.
 - PRIMARY PERMIT AND THE SUB PERMITS ARE EXPIRED AND
 NEED TO BE CLEARD PRIOR TO ADDITIONAL PERMITS BEING
 ISSUED. PLEASE CONTACT US OR STOP IN THE LOOK INTO THE
 PREVIOUS PERMITS.
  
 4) 314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS:
 - PLEASE SHOW LOCATION ON PLAN.
  
 5) 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET
 REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 - PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLISTS AND
 EPL CARD.
  
 6) 107.3.5.3 FBC [AMENDED]PROVIDE BASE FLOOD
 ELEVATION(B.F.E.) IN CERTIFICATE WITH DESIGN FLOOD
 ELEVATIONS TO INCLUDE ANY MECHANICAL EQUIPMENT AS
 APPLICABLE. ALL ELEVATION CERTIFICATES CERTIFIED
 OCTOBER 5, 2017 AND LATER ARE TO UTILIZE NAVD88 AND
 INCLUDE A CONVERSION TO NGVD29.
 - THIS FOUNDATION IS IN AE FLOOD ZONE WITH A REQUIRED
 BFE OF 12.1 PLUS THE CITY MANDATED 2 FOOT FREEBOARD.
 I'M LOOKING FOR TOP OF SLAB TO EXCEED 14.1 NAVD.
  
 7) 107.2.5 FBC[AMENDED] PROVIDE SURVEY OF PROPERTY
 SHOWING EASEMENTS AND DISTANCE FROM PROPERTY LINES TO
 NEW STRUCTURE. SURVEY TO INCLUDE SLAB ELEVATION AND
 SHOW POSITIVE DRAINAGE FROM FOUNDATION.
 - THIS EXISTING SLAB IS IN FLOOD ZONE AE AND WILL NEED
 TO HAVE A BASE FLOOD ELEVATION OF AT LEAST 14.1.
  
 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS AND DOORS.
  
 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 ROOFING.
  
 NOTES:
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  