| 2019-07-22 12:34:46 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19060706 |
| | REVIEWED: JULY 22, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 107.5.3 FBC[AMENDED] 107.2.1FBC[AMENDED] ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | -PLEASE ADD SIGNATURE OF RESPONSIBLE PARTY. |
| | |
| | 2) 501 FBC[EXISTING] LEVEL OF ALTERATION FOR WORK BEING |
| | PERFORMED. |
| | - THIS IS A NEW STRUCTURE AND NOT LEVEL II ALTERATION. |
| | PLEASE ADD OCCUPANCY CLASSIFICATION R-3. |
| | |
| | 3) WAS THE ADDITION WORK COMPLETED FROM PERMIT |
| | 02111028? DESCRIPTION SAYS ADDTION CONSISTING OF 2 |
| | BEDROOMS CLOET. |
| | - PRIMARY PERMIT AND THE SUB PERMITS ARE EXPIRED AND |
| | NEED TO BE CLEARD PRIOR TO ADDITIONAL PERMITS BEING |
| | ISSUED. PLEASE CONTACT US OR STOP IN THE LOOK INTO THE |
| | PREVIOUS PERMITS. |
| | |
| | 4) 314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS: |
| | - PLEASE SHOW LOCATION ON PLAN. |
| | |
| | 5) 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET |
| | REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE |
| | METHOD IN R401.2 AND SUPPLY DOCUMENTATION. |
| | - PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLISTS AND |
| | EPL CARD. |
| | |
| | 6) 107.3.5.3 FBC [AMENDED]PROVIDE BASE FLOOD |
| | ELEVATION(B.F.E.) IN CERTIFICATE WITH DESIGN FLOOD |
| | ELEVATIONS TO INCLUDE ANY MECHANICAL EQUIPMENT AS |
| | APPLICABLE. ALL ELEVATION CERTIFICATES CERTIFIED |
| | OCTOBER 5, 2017 AND LATER ARE TO UTILIZE NAVD88 AND |
| | INCLUDE A CONVERSION TO NGVD29. |
| | - THIS FOUNDATION IS IN AE FLOOD ZONE WITH A REQUIRED |
| | BFE OF 12.1 PLUS THE CITY MANDATED 2 FOOT FREEBOARD. |
| | I'M LOOKING FOR TOP OF SLAB TO EXCEED 14.1 NAVD. |
| | |
| | 7) 107.2.5 FBC[AMENDED] PROVIDE SURVEY OF PROPERTY |
| | SHOWING EASEMENTS AND DISTANCE FROM PROPERTY LINES TO |
| | NEW STRUCTURE. SURVEY TO INCLUDE SLAB ELEVATION AND |
| | SHOW POSITIVE DRAINAGE FROM FOUNDATION. |
| | - THIS EXISTING SLAB IS IN FLOOD ZONE AE AND WILL NEED |
| | TO HAVE A BASE FLOOD ELEVATION OF AT LEAST 14.1. |
| | |
| | 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AND DOORS. |
| | |
| | 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | ROOFING. |
| | |
| | NOTES: |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |