| 2019-06-20 14:49:32 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PANEL SCHEDULES PROVIDED ARE FOR PANEL MDP, SUBPANEL |
| | 1, AND SUBPANEL 2. THE RISER DIGRAM SHOWS A TRANSFER |
| | SWITCH AND THE SUBPANEL 1, SUBPANEL 2, AND POOL |
| | SUBPANEL. SUBPANEL 1 IS SHOWN AS 100 AMP IN RISER, AND |
| | AS 70 AMP IN PANEL SCHEDULE. PROVIDE ACCURATE RISER |
| | DIAGRAM AND FEEDERS, CORRECT DISCREPANCIES. NEC 215.5, |
| | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 |
| | 2. SUBPANEL 1 IS SHOWN AS BEING FED WITH # 6 WIRE, |
| | WHICH HAS AN AMPACITY OF 65 AMPS AT 75 DEGREE |
| | TERMINALS. THIS WIRE IS CURRENTLY OVERLOADED AS SHOWN |
| | WITH 69 AMPS ON B PHASE. PROVIDE LOAD CALCULATION FOR |
| | SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| | CAPACITY OF SERVICE IS ADEQUATE. PROVIDE CORRECTION. |
| | NEC 215.2 |
| | 3. SUBPANEL 1 IS SHOWN AS BEING LOCATED IN A BATHROOM, |
| | WHICH IS A CODE VIOLATION. PROVIDE CORRECTION. NEC |
| | 240.24(E); FBC RE E3705.7 |
| | 4. SUBPANEL 2 SHOWS A LOAD OF 20 AMPS FOR THE DRYER, |
| | BUT THERE IS NO LOAD INCLUDED IN THE LOAD CALCULATION |
| | FOR THE DRYER. PROVIDE CORRECTION. NEC 220; FBC RE |
| | E3602.2 |
| | 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |