Plan Review Notes
Plan Review Notes For Permit 19060677
Permit Number 19060677
Review Stop ENG
Sequence Number 3
Notes
Date Text
2019-09-17 07:16:09ORIGINAL COMMENT: PROVIDE CALCULATIONS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM &
 PEAK) AND FIRE FLOW DEMANDS FOR ADDITIONAL DOCKS.
 CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER AND PER
 FAC 64-E.008 FOR WATER.
  
 LATEST RESPONSE DATED AUGUST 28, 2019 STATES: "THE
 REVISED DEMAND CALC HAS BEEN ADDED TO THE CIVIL
 DRAWINGS."
  
 STILL UNABLE TO LOCATE WATER, SEWER AND FIRE FLOW
 DEMAND CALCULATIONS ON SUBMITTED SHEET C-1 OF
 KIMLEY-HORN CIVIL DRAWING DATED JUNE 2019.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  