| Plan Review Notes For Permit 19060677 |
| Permit Number |
19060677 |
|
| Review Stop |
ENG |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-09-17 07:16:09 | ORIGINAL COMMENT: PROVIDE CALCULATIONS OF EXISTING AND | | | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM & | | | PEAK) AND FIRE FLOW DEMANDS FOR ADDITIONAL DOCKS. | | | CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER AND PER | | | FAC 64-E.008 FOR WATER. | | | | | | LATEST RESPONSE DATED AUGUST 28, 2019 STATES: "THE | | | REVISED DEMAND CALC HAS BEEN ADDED TO THE CIVIL | | | DRAWINGS." | | | | | | STILL UNABLE TO LOCATE WATER, SEWER AND FIRE FLOW | | | DEMAND CALCULATIONS ON SUBMITTED SHEET C-1 OF | | | KIMLEY-HORN CIVIL DRAWING DATED JUNE 2019. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX | | | 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|