| 2019-08-14 14:32:27 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19060677 |
| | ADD: 4200 N. FLAGLER DR. RYBOVICH K DOCK |
| | CONT: BELLINGHAM MARINE |
| | TEL: 904-358-3362 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. JULY 01/2019 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) NOT COMPLIED. THE SMALLER PLANS THAT WERE SUBMITTED |
| | ARE NOT TO SCALES THAT ARE SPECIFIED ON THE DRAWINGS. |
| | THE PLANS ARE NOT SIGNED AND SEALED AS REQUIRED BY FAC |
| | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND |
| | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS, REPORTS |
| | OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND |
| | SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION |
| | 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MUST BE |
| | PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN |
| | BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | NOTE: ELECTRONIC OR DIGITAL SIGNATURES ARE ONLY |
| | ACCEPTABLE ON ELECTRONICALLY SUBMITTED PLANS. |
| | |
| | ORIGINAL COMMENT: |
| | THE SUBMITTED PLANS HAVE BEEN ENLARGED: |
| | 2A) WITH THE SUBMITTED PLANS BEING ENLARGED THE SEAL IS |
| | OVER 3 INCHES IN DIAMETER, THE SIGNATURE IS NO LONGER |
| | AN ORIGINAL SIGNATURE, IT HAS BEEN COPIED. 61G15-23.002 |
| | SEALS ACCEPTABLE TO THE BOARD. |
| | (2) SEALS, EMBOSSING SEALS AND DIGITALLY CREATED SEALS |
| | SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND |
| | SHALL BE OF A DESIGN SIMILAR TO THOSE SET FORTH IN |
| | SUBSECTIONS. |
| | |
| | 2B) SHEET 1 OF 19 INDICATES AN ENGINEERING SCALE OF 1 |
| | INCH = 50 FEET. THIS SCALE DOES NOT MEET THE |
| | REQUIREMENTS OF 107.2.1.3. QUALITY OF PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 |
| | INCH SCALE UPON SUBSTANTIAL PAPER. 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE. THE PLANS WERE ENLARGED TO A |
| | MEASUREMENT OF 51.33 FEET EQUALS 2 1/8 INCHES. IF THE |
| | PLANS ARE ENLARGED PLEASE CHANGE THE SCALE TO MATCH. |
| | |
| | 3) NOT COMPLIED. THE SITE PLAN THAT WAS SUBMITTED IS |
| | SUFFICIENT. HOWEVER, IT IS REQUIRED TO BE SIGNED AND |
| | SEALED BY THE ENGINEER AS REQUIRED BY FAC 61G15-23.003 |
| | PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH |
| | MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE |
| | PROVISIONS OF SECTION 471.025, F.S., AND RULE |
| | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED |
| | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL |
| | ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | NOTE: ELECTRONIC OR DIGITAL SIGNATURES ARE ONLY |
| | ACCEPTABLE ON ELECTRONICALLY SUBMITTED PLANS. |
| | |
| | ORIGINAL COMMENT: |
| | MISSING SURVEY SHOWING THE PROPERTY LINES AND OVERALL |
| | DISTANCE THE DOCKS ARE GOING INTO THE INTER-COASTAL |
| | WATER WAY. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4) NOT COMPLIED. THE SITE PLANS AND THE BELLINGHAM |
| | MARINE PLANS DO NOT MATCH THE PLANS THAT WERE APPROVED |
| | BY THE U.S. ARMY CORPS OF ENGINEERS ON AUGUST 29, 2017 |
| | AND THE FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION. |
| | THE FINGER PIERS RUN NORTH TO SOUTH ON THE CORPS AND |
| | FDEP APPROVED PLANS AND THEY ARE SHOWN EAST TO WEST ON |
| | THE BELLINGHAM MARINE PLANS. THERE ARE OTHER |
| | DISCREPANCIES AS WELL. PROVIDE DOCUMENTATION THAT THESE |
| | CHANGES ARE ACCEPTABLE TO THE CORPS AND THE FDEP. |
| | |
| | ORIGINAL COMMENT. |
| | WEST PALM BEACH MUNI CODE ARTICLE X SECTION 94-313 |
| | DOCKS (2) ADDITIONAL APPLICATION REQUIREMENTS, ( E ) |
| | VALID WRITTEN APPROVAL OF THE PROPOSED DOCK BY THE |
| | FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION (DEP), |
| | THE U.S. ARMY CORPS OF ENGINEERS (THE CORPS) AND/OR THE |
| | SOUTH FLORIDA WATER MANAGEMENT DISTRICT (SFWMD) IS |
| | REQUIRED. SUCH WRITTEN APPROVAL SHALL CONTAIN THE DATE |
| | ON WHICH THE PROPOSED DOCK WAS APPROVED. |
| | |
| | 5) NOT COMPLIED. THIS PROJECT IS EXPOSURE CATEGORY D |
| | AND THE PLANS SPECIFY C. PLEASE CORRECT. FBC 1609.4.3 |
| | |
| | ORIGINAL COMMENT: |
| | SHEET 2 OF 19 WIND DESIGN IS FOR 140 MPH (DOES NOT |
| | STATE IF THIS IS VULT OR VASD) UNOCCUPIED. |
| | 5A) THE 2ND ISSUE IS THE WIND DESIGN DOES NOT PROVIDE |
| | AT WHAT EXPOSURE THE WIND DESIGN IS TAKEN. |
| | 5B) THE 3RD ITEM STATES THE OWNER IS RESPONSIBLE FOR |
| | WIND / WAVE STUDY TO VERIFY THE CONDITIONS, NOT |
| | PROVIDED. |
| | 5C) 4TH ITEM ALL ELEVATIONS ARE IN NGVD. SINCE OCT. |
| | 11/2017 THE WEST PALM BUILDING DEPARTMENT HAS CHANGED |
| | TO NAVD 88 FOR ALL MEASUREMENTS DEALING WITH WATER WAYS |
| | AND FLOOD WAYS TO COINCIDE WITH THE NEW FLOOD MAPS. |
| | |
| | 5D) COMPLIED. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |