Plan Review Notes
Plan Review Notes For Permit 19060677
Permit Number 19060677
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-26 10:42:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COVER SHEET - THERE ARE NO INDICATIONS OF COMPLAINCE
 WITH ANY FIRE CODE.
  
 AT MINIMUM THE PROPOSED SHALL COMPLY WITH NFPA 1 & 101,
 2015 EDITIONS, NFPA 303, 2011 EDITION, NFPA 70, 2014,
 AS WELL AS, ALL ASSOCIATED CODES.
  
 PLEASE REVIEW THE SUBMITTAL TO ENSURE COMPLIANCE AND
 PROVIDED A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE.
  
  
 1A) THERE IS NO SCOPE OF WORK PROVIDED THAT MAY HELP
 ADDRESS SOME OF THE COMMENTS BELOW. HOWEVER, PLEASE
 PROVIDE RESPONES TO THE BELOW FOR THE RECORD.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK
  
  
  
 2) SHEET 1 OF 19 - THOUGH THERE IS AN INDICATION OF 3
 NORTHERN FINGER PIERS BEING EXISTING, IT IS UNCLEAR
 WHAT WILL BE NEW.
  
 THERE ARE SOME AREAS SHADED THAT ARE ATTACHED TO
 DARKENED AREAS.
  
 PLEASE PROVIDE CLARITY ON WHAT IS EXISTING AND WHAT IS
 PROPOSED OR REPLACED.
  
  
  
 3) SHEET 3 OF 19 - THERE ARE INDICATION OF STANDPIPE
 AND FIRE EXTINGUISHER LOCATION BUT NO DETAILS,
 INCLUDING WHICH ONES ARE EXISTING VS PROPOSED.
  
 PLEASE CLARIFY AND PROVIDE DIMENSIONS IN COMPLIANCE
 WITH NFPA 303 FIRE PROTECTION STANDARD FOR MARINAS AND
 BOATYARDS 2011 EDITION
  
 6.4* FIRE STANDPIPE SYSTEMS.
 6.4.1 CLASS I STANDPIPE SYSTEMS SHALL BE PROVIDED FOR
 PIERS,
 BULKHEADS, AND BUILDINGS WHERE THE HOSE LAY DISTANCE
 FROM THE
 FIRE APPARATUS EXCEEDS 150 FT (45 M).
  
 6.4.3 STANDPIPE SYSTEMS, WHERE INSTALLED, SHALL BE IN
 ACCORDANCE
 WITH NFPA14, STANDARD FOR THE INSTALLATION OF STANDPIPE
 AND
 HOSE SYSTEMS, EXCEPT FOR THE PROVISIONS IDENTIFIED IN
 6.4.4
 THROUGH 6.4.7.
 6.4.4 HOSE RACKS, HOSES, AND STANDPIPE CABINETS SHALL
 NOT BE
 REQUIRED ON PIERS AND BULKHEADS.
 6.4.5 SUPPLY PIPING FOR STANDPIPES ON PIERS AND
 BULKHEADS
 SHALL BE SIZED FOR THE MINIMUM FLOW RATE FOR CLASS II
 SYSTEMS.
 6.4.6 MANUAL DRY STANDPIPES SHALL BE PERMITTED.
 6.4.7 FLEXIBLE CONNECTIONS SHALL BE PERMITTED ON
 FLOATING
 PIERS WHERE ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE.
  
  
 4) ALL STANDPIPE WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS IN COMPLIANCE WITH NFPA 303.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE
  
  
  
 5) THERE ARE NO INDICATIONS OF ELECTRICAL WORK.
  
 WILL ELECTIRCAL WORK BE DONE UNDER SEPARATE PERMIT?
  
 PLEASE CLARIFY AND PROVIDE A NOTE.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  