| 2019-06-26 10:42:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) COVER SHEET - THERE ARE NO INDICATIONS OF COMPLAINCE |
| | WITH ANY FIRE CODE. |
| | |
| | AT MINIMUM THE PROPOSED SHALL COMPLY WITH NFPA 1 & 101, |
| | 2015 EDITIONS, NFPA 303, 2011 EDITION, NFPA 70, 2014, |
| | AS WELL AS, ALL ASSOCIATED CODES. |
| | |
| | PLEASE REVIEW THE SUBMITTAL TO ENSURE COMPLIANCE AND |
| | PROVIDED A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE. |
| | |
| | |
| | 1A) THERE IS NO SCOPE OF WORK PROVIDED THAT MAY HELP |
| | ADDRESS SOME OF THE COMMENTS BELOW. HOWEVER, PLEASE |
| | PROVIDE RESPONES TO THE BELOW FOR THE RECORD. |
| | |
| | PLEASE PROVIDE A DETAILED SCOPE OF WORK |
| | |
| | |
| | |
| | 2) SHEET 1 OF 19 - THOUGH THERE IS AN INDICATION OF 3 |
| | NORTHERN FINGER PIERS BEING EXISTING, IT IS UNCLEAR |
| | WHAT WILL BE NEW. |
| | |
| | THERE ARE SOME AREAS SHADED THAT ARE ATTACHED TO |
| | DARKENED AREAS. |
| | |
| | PLEASE PROVIDE CLARITY ON WHAT IS EXISTING AND WHAT IS |
| | PROPOSED OR REPLACED. |
| | |
| | |
| | |
| | 3) SHEET 3 OF 19 - THERE ARE INDICATION OF STANDPIPE |
| | AND FIRE EXTINGUISHER LOCATION BUT NO DETAILS, |
| | INCLUDING WHICH ONES ARE EXISTING VS PROPOSED. |
| | |
| | PLEASE CLARIFY AND PROVIDE DIMENSIONS IN COMPLIANCE |
| | WITH NFPA 303 FIRE PROTECTION STANDARD FOR MARINAS AND |
| | BOATYARDS 2011 EDITION |
| | |
| | 6.4* FIRE STANDPIPE SYSTEMS. |
| | 6.4.1 CLASS I STANDPIPE SYSTEMS SHALL BE PROVIDED FOR |
| | PIERS, |
| | BULKHEADS, AND BUILDINGS WHERE THE HOSE LAY DISTANCE |
| | FROM THE |
| | FIRE APPARATUS EXCEEDS 150 FT (45 M). |
| | |
| | 6.4.3 STANDPIPE SYSTEMS, WHERE INSTALLED, SHALL BE IN |
| | ACCORDANCE |
| | WITH NFPA14, STANDARD FOR THE INSTALLATION OF STANDPIPE |
| | AND |
| | HOSE SYSTEMS, EXCEPT FOR THE PROVISIONS IDENTIFIED IN |
| | 6.4.4 |
| | THROUGH 6.4.7. |
| | 6.4.4 HOSE RACKS, HOSES, AND STANDPIPE CABINETS SHALL |
| | NOT BE |
| | REQUIRED ON PIERS AND BULKHEADS. |
| | 6.4.5 SUPPLY PIPING FOR STANDPIPES ON PIERS AND |
| | BULKHEADS |
| | SHALL BE SIZED FOR THE MINIMUM FLOW RATE FOR CLASS II |
| | SYSTEMS. |
| | 6.4.6 MANUAL DRY STANDPIPES SHALL BE PERMITTED. |
| | 6.4.7 FLEXIBLE CONNECTIONS SHALL BE PERMITTED ON |
| | FLOATING |
| | PIERS WHERE ACCEPTABLE TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE. |
| | |
| | |
| | 4) ALL STANDPIPE WORK SHALL BE DONE UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS IN COMPLIANCE WITH NFPA 303. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| | AND COMPLIANCE |
| | |
| | |
| | |
| | 5) THERE ARE NO INDICATIONS OF ELECTRICAL WORK. |
| | |
| | WILL ELECTIRCAL WORK BE DONE UNDER SEPARATE PERMIT? |
| | |
| | PLEASE CLARIFY AND PROVIDE A NOTE. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |