| 2019-07-01 12:59:49 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19060677 |
| | ADD: 4200 N. FLAGLER DR. RYBOVICH K DOCK |
| | CONT: BELLINGHAM MARINE |
| | TEL: 904-358-3362 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 01/2019 |
| | ACTION: DENIED |
| | |
| | 1) NOTICE. UNDER THE HEADING OF COMPANY NAME (DBA) IS |
| | LISTED AS FLORIDA FLOATS THIS IS NOT THE LISTED DBA |
| | WITH THE STATE. BELLINGTON MARINE IS. FLORIDA FLOATS |
| | HAS BEEN STRUCK. |
| | |
| | 2) THE SUBMITTED PLANS HAVE BEEN ENLARGED: |
| | 2A) WITH THE SUBMITTED PLANS BEING ENLARGED THE SEAL IS |
| | OVER 3 INCHES IN DIAMETER, THE SIGNATURE IS NO LONGER |
| | AN ORIGINAL SIGNATURE, IT HAS BEEN COPIED. 61G15-23.002 |
| | SEALS ACCEPTABLE TO THE BOARD. |
| | (2) SEALS, EMBOSSING SEALS AND DIGITALLY CREATED SEALS |
| | SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND |
| | SHALL BE OF A DESIGN SIMILAR TO THOSE SET FORTH IN |
| | SUBSECTIONS. |
| | |
| | 2B) SHEET 1 OF 19 INDICATES AN ENGINEERING SCALE OF 1 |
| | INCH = 50 FEET. THIS SCALE DOES NOT MEET THE |
| | REQUIREMENTS OF 107.2.1.3. QUALITY OF PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 |
| | INCH SCALE UPON SUBSTANTIAL PAPER. 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE. THE PLANS WERE ENLARGED TO A |
| | MEASUREMENT OF 51.33 FEET EQUALS 2 1/8 INCHES. IF THE |
| | PLANS ARE ENLARGED PLEASE CHANGE THE SCALE TO MATCH. |
| | |
| | 3) MISSING SURVEY SHOWING THE PROPERTY LINES AND |
| | OVERALL DISTANCE THE DOCKS ARE GOING INTO THE |
| | INTER-COASTAL WATER WAY. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 4) WEST PALM BEACH MUNI CODE ARTICLE X SECTION 94-313 |
| | DOCKS (2) ADDITIONAL APPLICATION REQUIREMENTS, ( E ) |
| | VALID WRITTEN APPROVAL OF THE PROPOSED DOCK BY THE |
| | FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION (DEP), |
| | THE U.S. ARMY CORPS OF ENGINEERS (THE CORPS) AND/OR THE |
| | SOUTH FLORIDA WATER MANAGEMENT DISTRICT (SFWMD) IS |
| | REQUIRED. SUCH WRITTEN APPROVAL SHALL CONTAIN THE DATE |
| | ON WHICH THE PROPOSED DOCK WAS APPROVED. |
| | |
| | 5) SHEET 2 OF 19 WIND DESIGN IS FOR 140 MPH (DOES NOT |
| | STATE IF THIS IS VULT OR VASD) UNOCCUPIED. |
| | 5A) THE 2ND ISSUE IS THE WIND DESIGN DOES NOT PROVIDE |
| | AT WHAT EXPOSURE THE WIND DESIGN IS TAKEN. |
| | 5B) THE 3RD ITEM STATES THE OWNER IS RESPONSIBLE FOR |
| | WIND / WAVE STUDY TO VERIFY THE CONDITIONS, NOT |
| | PROVIDED. |
| | 5C) 4TH ITEM ALL ELEVATIONS ARE IN NGVD. SINCE OCT. |
| | 11/2017 THE WEST PALM BUILDING DEPARTMENT HAS CHANGED |
| | TO NAVD 88 FOR ALL MEASUREMENTS DEALING WITH WATER WAYS |
| | AND FLOOD WAYS TO COINCIDE WITH THE NEW FLOOD MAPS. |
| | |
| | 5D) LENGTH OF PILING/ DEPTH OF REQUIRED PENETRATION. |
| | DETERMINED BY THE DAMES & MOORE GEOTECHNICAL REPORT. NO |
| | SUCH REPORT WAS SUBMITTED. ADDITIONAL INFORMATION IS |
| | REQUIRED. 107.2.1.2. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN REQUIRED REPORTS & |
| | PLANS AND REQUIRED DOCUMENTATION. WITH THE NEXT PLAN |
| | REVIEW CYCLE THERE MAYBE ADDITIONAL REVIEW COMMENTS |
| | BECAUSE OF NEW PLANS AND INFORMATION LACKING UNDER THE |
| | PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |