| 2019-08-01 08:24:07 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19060662 |
| | 2ND REVIEW: AUGUST 1, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) OK |
| | |
| | 2) OK |
| | |
| | 3) OK |
| | |
| | 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AND DOOR. |
| | PRODUCT APPROVALS WERE NOT PROVIDED. |
| | PLEASE PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOOR. |
| | |
| | ADDITIONAL COMMENT: |
| | 5) 311.3 FBC[R]FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT |
| | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| | DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED |
| | IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR |
| | LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS |
| | HORIZONTAL (2 PERCENT). |
| | 311.3.1 FBC[R]FLOOR ELEVATIONS AT THE REQUIRED EGRESS |
| | DOORS. LANDINGS OR FINISHED FLOORS AT THE REQUIRED |
| | EGRESS DOOR SHALL BE NOT MORE THAN 11/2 INCHES (38 MM) |
| | LOWER THAN THE TOP OF THE THRESHOLD. |
| | EXCEPTION: THE LANDING OR FLOOR ON THE EXTERIOR SIDE |
| | SHALL BE NOT MORE THAN 73/4 INCHES (196 MM) BELOW THE |
| | TOP OF THE THRESHOLD. |
| | |
| | PLEASE LOOK AT LANDING FOR FRONT DOOR. |
| | |