| 2019-07-25 17:39:29 | RESIDENTIAL (R3) MECHANICAL REVISION SECOND CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- OK. | | | | | | 2- MECHANICAL REVIEW WAS APPROVED ON 04/02/18 WITH THE | | | PROVISO REQUESTING ENERGY CALCULATIONS TO BE REVISED TO | | | MATCH EQUIPMENT. REVISED ENERGY CALCULATIONS WERE NOT | | | SUBMITTED. NEED TO SUBMIT REVISED ENERGY CALCULATIONS. | | | SEE COPY OF PROVISO BELOW. | | | | | | RESPONSE: | | | REPEAT COMMENT. ENERGY CALCULATIONS WERE NOT REVISED. | | | | | | | | | | | | | | | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | 1- REVISE THE SEER EFFICIENCY SHOWN ON THE ENERGY | | | CALCULATIONS TO MATCH SEER SHOWN ON A/C PLANS AND | | | EQUIPMENT AHRI CERTIFICATE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|