Plan Review Notes
Plan Review Notes For Permit 19060644
Permit Number 19060644
Review Stop G
Sequence Number 2
Notes
Date Text
2019-08-15 16:24:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54= NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 GAS COMMENTS: DENIED
 1) ?? SIZE FOR CSST IS NOT CORRECT. PROVIDE EHD TUBE
 SIZE(S) FOR CSST. RISER DIAGRAM IS SOMEWHAT UNCLEAR.
 DROP TO DRYER IS OBSCURING INFORMATION FOR HORIZONTAL
 RUN TO TANKLESS HEATER AND SOME DIMENSIONS ARE
 DIFFICULT TO READ. PER WPB FBC 107.2.1 PROVIDE A
 LEGIBLE RISER DIAGRAM.
 2) BTU INFO IS BARELY LEGIBLE ON RANGE SUBMITTAL.
 3) I CANNOT FIND BTU INFO ON THE DRYER SUBMITTAL.
 4) SECOND REQUEST: SUBMIT COMBUSTION AIR CALCULATIONS
 FOR THE ADDED GAS APPLIANCES. WHERE COMBUSTION AIR IS
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR. 2017 FBCR G2407.9.3.
 5) PROVIDE SPEC FOR MP REGULATORS FOR APPLIANCES AND
 INCLUDE VENT LIMITER FOR INDOOR REGULATORS. OUTDOOR
 REGULATORS SHALL BE RATED FOR OUTDOOR USE.
 6) SHOW LOCATION OF GAS METER ON THE BUILDING PLANS.
  