| 2019-08-15 16:24:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54= NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | GAS COMMENTS: DENIED |
| | 1) ?? SIZE FOR CSST IS NOT CORRECT. PROVIDE EHD TUBE |
| | SIZE(S) FOR CSST. RISER DIAGRAM IS SOMEWHAT UNCLEAR. |
| | DROP TO DRYER IS OBSCURING INFORMATION FOR HORIZONTAL |
| | RUN TO TANKLESS HEATER AND SOME DIMENSIONS ARE |
| | DIFFICULT TO READ. PER WPB FBC 107.2.1 PROVIDE A |
| | LEGIBLE RISER DIAGRAM. |
| | 2) BTU INFO IS BARELY LEGIBLE ON RANGE SUBMITTAL. |
| | 3) I CANNOT FIND BTU INFO ON THE DRYER SUBMITTAL. |
| | 4) SECOND REQUEST: SUBMIT COMBUSTION AIR CALCULATIONS |
| | FOR THE ADDED GAS APPLIANCES. WHERE COMBUSTION AIR IS |
| | PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION |
| | SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| | COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| | VENTILATION AIR. 2017 FBCR G2407.9.3. |
| | 5) PROVIDE SPEC FOR MP REGULATORS FOR APPLIANCES AND |
| | INCLUDE VENT LIMITER FOR INDOOR REGULATORS. OUTDOOR |
| | REGULATORS SHALL BE RATED FOR OUTDOOR USE. |
| | 6) SHOW LOCATION OF GAS METER ON THE BUILDING PLANS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19060644 127 WESTMINSTER RD |
| | |