Plan Review Notes
Plan Review Notes For Permit 19060644
Permit Number 19060644
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-08 10:52:51PLUMBING 1ST REVIEW**DENIED**
  
 1) PLUMBING ISOMETRIC SHOW DRAIN TO WASHING MACHINE AS
 2". FBC-P 709.1, 406.2 CALLS FOR MIN 3" TO THE FIXTURE
 DRAIN OR STACK.
  
 2) PROVIDE LOCATION OF WATER HEATER. ALL NEW HOT WATER
 PIPING WILL REQUIRED MIN R-3 INSULATIONS. FBC-ENERGY
 R403.5.3
  
 3) PLUMBING ISOMETRIC FOR NEW BATHROOM DOES NOT SHOW IT
 CONNECTING TO THE BUILDING DRAIN. FBC 107.3.5
  
 4) PLAN SHOWS TUB/ SHOWER VALVES AS 2 HANDLE. 2 HANDLE
 VALVES NO LONGER MEET THE CODE AND MUST BE PRESSURE
 BALANCE, THERMOSTATIC, OR A COMBO OF BOTH AND HAVE A
 STOP LIMITER MAX 120F. PROVIDE MANUFACTURE INSTALLATION
 MANUAL. FBC 107.2.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  