| Plan Review Notes For Permit 19060644 |
| Permit Number |
19060644 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-08 10:52:51 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PLUMBING ISOMETRIC SHOW DRAIN TO WASHING MACHINE AS | | | 2". FBC-P 709.1, 406.2 CALLS FOR MIN 3" TO THE FIXTURE | | | DRAIN OR STACK. | | | | | | 2) PROVIDE LOCATION OF WATER HEATER. ALL NEW HOT WATER | | | PIPING WILL REQUIRED MIN R-3 INSULATIONS. FBC-ENERGY | | | R403.5.3 | | | | | | 3) PLUMBING ISOMETRIC FOR NEW BATHROOM DOES NOT SHOW IT | | | CONNECTING TO THE BUILDING DRAIN. FBC 107.3.5 | | | | | | 4) PLAN SHOWS TUB/ SHOWER VALVES AS 2 HANDLE. 2 HANDLE | | | VALVES NO LONGER MEET THE CODE AND MUST BE PRESSURE | | | BALANCE, THERMOSTATIC, OR A COMBO OF BOTH AND HAVE A | | | STOP LIMITER MAX 120F. PROVIDE MANUFACTURE INSTALLATION | | | MANUAL. FBC 107.2.1 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | | | | |
|