| Plan Review Notes For Permit 19060644 |
| Permit Number |
19060644 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-08 10:40:57 | GAS 1ST REVIEW**DENIED** | | | | | | 1) A GAS PLAN AND PERMIT ARE REQUIRED. FBC 105.1 | | | | | | 2) PROVIDE STOVE MANUFACTURES INSTALLATION MANUAL. FBC | | | 107.2.1 | | | | | | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS | | | APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE | | | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | | ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBCR | | | G2407.9.3. | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | | | | |
|