| Plan Review Notes For Permit 19060624 |
| Permit Number |
19060624 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-17 07:11:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1003.6, REVISE THE FLOOR PLAN TO NOTE IF THE | | | OPENINGS ARE DOORS, WINDOWS, OR BOTH. IF DOORS ARE | | | INCLUDED IN SCOPE OF WORK, A LIFE SAFETY PLAN IS | | | REQUIRED TO SHOW HOW EXITING IS AFFECTED. | | | | | | 2. FBC B 1609, ELCO TAPCONS ARE NOT ONE OF THE | | | FASTENERS INCLUDED IN THE PRODUCT APPROVAL, SEE PAGE | | | 13; REVISE INSTALLATION SCHEDULE ACCORDINGLY. | | | | | | 3. FBC 107, TWO COMPLETE SETS OF PERMIT DOCUMENTS | | | REQUIRED FOR PERMIT ISSUANCE. | | | | | | |
|