2019-07-01 16:25:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060617
 7/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE CORRIDOR SHALL NOT BE USED TO RETURN
 AIR UNLESS EXCEPTION 3 UNDER SECTION 601.2 FBC IS
 APPLICABLE. PLEASE INDICATE THE SQUARE FOOTAGE OF THE
 SPACE. IF UNDER 1000 S.F. USE OF THE CORRIDOR IS
 PERMITTED.
  
 2) M1: SIZING OF THE RETURN TRANSFER DUCTS IS DEPENDENT
 ON KNOWING THE SIZES OF THE SUPPLY DUCTS IN THE ROOM-
 SEE SECTION 601.6 EXCEPTION 1. PLEASE SHOW THE SUPPLY
 DUCTS AND SIZES ON THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  