| 2019-08-14 13:54:13 | 2ND REVIEW: 19060602 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE SANITARY ISOMETRIC DRAWING HAS THE FOLLOWING |
| | CODE VIOLATIONS. |
| | A) THE MASTER BATHROOM IS MISSING THE SHOWER. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | B) THE CHRIS BATHROOM THE TOILET AND THE BATH TUB ARE |
| | NOT VENTED PROPERLY THEY SHALL BE VENTED BY THE |
| | LAVATORY. PER FBC RES P3108.1 |
| | C) THE ROSA BATHROOM THE TOILET AND THE BATH TUB ARE |
| | NOT VENTED PROPERLY THEY SHALL BE VENTED BY THE |
| | LAVATORY. PER FBC RES P3108.1 |
| | |
| | 2. THE SANITARY ISOMETRIC DOES NOT MATCH THE PIPING |
| | LAYOUT ON THE FLOOR PLAN THEY SHOULD MATCH. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |