| Plan Review Notes For Permit 19060602 |
| Permit Number |
19060602 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-17 16:13:36 | GAS 1ST REVIEW**DENIED** | | | | | | 1) A COMPLETE GAS PLAN WITH INSTALLATION MANUALS IS | | | REQUIRED FOR A GAS PLAN REVIEW. GENERATOR WILL HAVE A | | | STAND ALONE PERMIT. | | | | | | 2) PROVIDE DISTANCE ON PLAN THAT EACH TANKLESS IS FROM | | | ANY DOOR OR WINDOW THAT OPENS. FBC 107.3.5 | | | | | | 3) PROVIDED R405-2017 ENERGY FORM CALLS OUT TANKLESS | | | WATER HEATER AS .60 E.F. THE MIN FEDERAL E.F IS | | | CURRENTLY .82. PLEASE REVISE YOUR R405-2017 FORM AND | | | RESUBMIT. DOE FEDERAL REGISTER VOL 81, NO 250 | | | | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|