2021-01-22 10:44:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) MAINS "A" AND "B" ARE THEY GROUPED AS REQUIRED BY
 230.72
  
 230.72 GROUPING OF DISCONNECTS (A) GENERAL. THE TWO TO
 SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE
 GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE
 THE LOAD SERVED
  
 2) RISER SHOWS JUST 1 #4 TO DISCONNECT "A"
  
 3) RISER SHOWS PANEL "B" AS A MAIN BREAKER PANEL AND
 PANEL SCHEDULE SHOWS MAIN LUG ONLY IF REMOTE AND IN
 ANOTHER STRUCTURE IT HAS TO BE MAIN BREAKER TYPE.
 225.33