| Notes |
| Date |
Text |
| 2021-01-22 10:44:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) MAINS "A" AND "B" ARE THEY GROUPED AS REQUIRED BY | | | 230.72 | | | | | | 230.72 GROUPING OF DISCONNECTS (A) GENERAL. THE TWO TO | | | SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE | | | GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE | | | THE LOAD SERVED | | | | | | 2) RISER SHOWS JUST 1 #4 TO DISCONNECT "A" | | | | | | 3) RISER SHOWS PANEL "B" AS A MAIN BREAKER PANEL AND | | | PANEL SCHEDULE SHOWS MAIN LUG ONLY IF REMOTE AND IN | | | ANOTHER STRUCTURE IT HAS TO BE MAIN BREAKER TYPE. | | | 225.33 |
|