Plan Review Notes
Plan Review Notes For Permit 19060556
Permit Number 19060556
Review Stop E
Sequence Number 3
Notes
Date Text
2020-11-19 09:34:10CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 PREVIOUS COMMENTS:
  
 1. RISER DIAGRAM SHOWS 3/0 WIRE FEEDING A 350 AMPS
 SERVICE. THIS WIRE IS NOT RATED FOR 350 AMPS SERVICE.
 PROVIDE CORRECTION. NEC 310.15(B)(7); FBC RE E3603.1
  
 NOT CORRECTED.
  
 RISER DIAGRAM SHOWS A (1) 4/0 EXISTING CONDUCTOR FOR
 THE OVERHEAD SERVICE TO FPL TRANSFORMER AND (1) 4/0
 FROM EXISTING METER TO EXISTING 350 AMPS SERVICE
 DISCONNECT. THIS IS NOT ENOUGH FOR A 350 AMPS SERVICE
 AND IT SHOULD BE AT LEAST 3 CONDUCTORS OR TWO SETS OF
 THE PROPERLY SIZED CONDUCTORS. PLEASE CORRECT.
  
  
 2. ON RISER DIAGRAM, WIRE FROM MAIN DISCONNECT TO
 INTERIOR PANELS SHOULD INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6
  
 NOT CORRECTED.
  
 STILL MISSING ON NEW RISER DIAGRAM. EACH FEEDER TO
 PANEL A AND TO PANEL B SHOULD HAVE 4 CONDUCTORS, THE
 3#3/0 PLUS THE EQUIPMENT GROUNDING CONDUCTOR SIZED AS
 PER NEC 250-122; FBC RE E3704.6. PLEASE PROVIDE THE
 ACTUAL SIZE OF THE GROUNDING EQUIPMENT CONDUCTOR. A
 NOTE INDICATING TO SIZE THEM AS PER NEC 250-122 IS NOT
 ENOUGH.
  
 3. UNDER THE TITLE FOR NEW ELECTRIC ONLY, AFCI
 PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
  
 PARTIALLY CORRECTED BUT LANGUAGE INDICATING THAT SOME
 AREAS REQUIRE BOTH AFCI AND GFI IS VAGUE. ONE OPTION IS
 TO INDICATE IN PANEL SCHEDULE WHAT CIRCUITS HAVE AFCI
 OR GFCI OR BOTH.
  
 4. UNDER THE TITLE FOR NEW ELECTRIC ONLY AND NOTE 14,
 NOTE STATES THAT RECEPTACLES SHALL BE TAMPER RESISTANT
 PER NEC 406.11. THIS CODE SECTION DOES NOT APPLY TO
 TAMPER RESISTANT RECEPTACLES. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
  
 CORRECTED.
  
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 NEC 220; FBC RE E3602.2
  
 DOES THE TOTAL LOAD FOR EXISTING PANEL A INCLUDES THE
 LOAD FOR NEW PANEL B? TOTAL LOAD OF 99 AMPS SEEMS SMALL
 FOR A 350 AMPS SERVICE.
  
  
 6. IT APPEARS THIS PANEL IS LOCATED IN A SEPARATE
 STRUCTURE FROM THE BUILDING THAT HAS THE MAIN SERVICE.
 IF THIS IS THE CASE, PANEL B WILL NEED TO EITHER HAVE A
 MAIN BREAKER, OR A DISCONNECT AHEAD OF IT AT THE
 STRUCTURE. PROVIDE CORRECTION. NEC 225.31, 225.32
  
 NOT CLEAR. PANEL SCHEDULE FOR PANEL B DESCRIBES THE
 PANEL AS MAIN LUGS ONLY (MLO) BUT RISER DIAGRAM
 DESCRIBES PANEL B HAS HAVING A MAIN CIRCUIT BREAKER
 (MCB). IF PANEL B HAS A MAIN CIRCUIT BREAKER, PLEASE
 PROVIDE SIZE IN AMPS AND IF MLO PLEASE PROVIDE SIZE OF
 DISCONNECT AHEAD OF IT AT STRUCTURE AND SHOW IT ON
 RISER DIAGRAM.
  
  
 ADDITIONAL COMMENTS:
  
 7. PLEASE PROVIDE LOCATION OF MAIN SERVICE DISCONNECT,
 EXISTING PANEL A, NEW PANEL B. POWER LAYOUT SHOWS A NEW
 PANEL A LOCATED IN GARAGE, BUT RISER DIAGRAM DESCRIBES
 PANEL A AS EXISTING. PLEASE CORRECT AND CLEARLY SHOW
 LOCATION OF ALL THESE ELEMENTS.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  