Plan Review Notes
Plan Review Notes For Permit 19060556
Permit Number 19060556
Review Stop P
Sequence Number 2
Notes
Date Text
2019-10-24 12:41:43PLUMBING COMMENTS: APPROVED W/PROVISO
 1.CONCRETE TIE BEAMS OR BOND BEAMS SHALL NOT BE CUT,
 DRILLED, NOTCHED OR MODIFIED IN ANY WAY WITHOUT A
 DETAIL SIGNED AND SEALED BY A DULY LICENCED DESIGN
 PROFESSIONAL WHICH SHALL BE SUBMITTED TO THE BUILDING
 DEPARTMENT, APPROVED AND IN PLACE PRIOR TO INSPECTION.
 CONTRACTOR PROCEEDS AT THEIR OWN RISK.
 2.HORIZONTAL PIPING PASSING THROUGH WOOD FRAME STUDS
 SHALL BE INSTALLED IN ACCORDANCE WITH FBC RES R602.6
 DRILLING AND NOTCHING OF STUDS SHALL BE IN ACCORDANCE
 WITH THE FOLLOWING:
 A. NOTCHING. ANY STUD IN AN EXTERIOR WALL OR BEARING
 PARTITION SHALL BE PERMITTED TO BE CUT OR NOTCHED TO A
 DEPTH NOT EXCEEDING 25 PERCENT OF ITS WIDTH. STUDS IN
 NONBEARING PARTITIONS SHALL BE PERMITTED TO BE NOTCHED
 TO A DEPTH NOT TO EXCEED 40 PERCENT OF A SINGLE STUD
 WIDTH.
 B. DRILLING. ANY STUD SHALL BE PERMITTED TO BE BORED OR
 DRILLED, PROVIDED THAT THE DIAMETER OF THE RESULTING
 HOLE IS NOT MORE THAN 60 PERCENT OF THE STUD WIDTH, THE
 EDGE OF THE HOLE IS NOT MORE THAN 5/8 INCH (16 MM) TO
 THE EDGE OF THE STUD, AND THE HOLE IS NOT LOCATED IN
 THE SAME SECTION AS A CUT OR NOTCH. STUDS LOCATED IN
 EXTERIOR WALLS OR BEARING PARTITIONS DRILLED OVER 40
 PERCENT AND UP TO 60 PERCENT SHALL BE DOUBLED WITH NOT
 MORE THAN TWO SUCCESSIVE DOUBLED STUDS BORED. FOR
 CLARIFICATION, REFER TO FIGURES R602.6(1) AND R602.6(2)
 IN THE FLORIDA RESIDENTIAL CODE 2017 6TH EDITION (FBC
 RES).
 EXCEPTION: USE OF APPROVED STUD SHOES IS PERMITTED
 WHERE THEY ARE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S RECOMMENDATIONS.
 3.VERTICAL VENTS PASSING THROUGH WOOD FRAME TOP PLATES
 SHALL BE INSTALLED IN ACCORDANCE WITH FBC RES R602.6.1
 WHEN PIPING OR DUCTWORK IS PLACED IN OR PARTLY IN AN
 EXTERIOR WALL OR INTERIOR LOAD-BEARING WALL,
 NECESSITATING CUTTING, DRILLING OR NOTCHING OF THE TOP
 PLATE BY MORE THAN 50 PERCENT OF ITS WIDTH, A
 GALVANIZED METAL TIE NOT LESS THAN 0.054 INCH THICK
 (1.37 MM) (16 GA) AND 11/2 INCHES (38 MM) WIDE SHALL BE
 FASTENED ACROSS AND TO THE PLATE AT EACH SIDE OF THE
 OPENING WITH NOT LESS THAN EIGHT 10D (0.148 INCH
 DIAMETER) NAILS HAVING A MINIMUM LENGTH OF 11/2 INCHES
 (38 MM) AT EACH SIDE OR EQUIVALENT. THE METAL TIE MUST
 EXTEND A MINIMUM OF 6 INCHES PAST THE OPENING. FOR
 CLARIFICATION, REFER TO FIGURES R602.6.1 IN THE FLORIDA
 RESIDENTIAL CODE 2017 6TH EDITION (FBC RES).
 EXCEPTION: WHEN THE ENTIRE SIDE OF THE WALL WITH THE
 NOTCH OR CUT IS COVERED BY WOOD STRUCTURAL PANEL
 SHEATHING.
 4. PER WPB FBC 107.2.1, PROVIDE AS A DEFERRED
 SUBMITTAL, THE SUPPORTING DOCUMENT PREVIOUSLY PROVIDED
 FOR THE TANKLESS WATER HEATER AND SPECIFY ON THE
 DOCUMENT WHICH MODEL WATER HEATER IS TO BE FURNISHED.
 THE DOCUMENT SHALL BE SUBMITTED TO THE BUILDING
 DEPARTMENT WITH ARCHITECT?S STAMP, APPROVED AND ON SITE
 PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK.
 5. PER FBC RES P26094.4, MAINTAIN A DISTANCE BETWEEN
 THE TRENCHING FOR THE BUILDING SEWER RUNNING PARALLEL
 TO THE BUILDING FOUNDATION EDGE THAT KEEPS THE TRENCH
 OUT OF THE 45 DEGREE ANGLE OF REPOSE. SEE REDLINED
 COMMENT ON SANITARY PLAN VIEW.
 6. PER FBC RES P3105.1, THE VENT FOR THE BAR SINK SHALL
 NOT CONNECT BELOW THE TRAP WEIR AND PER FBC RES P3104.4
 SHALL CONNECT TO THE TOP OF THE TRAP CONNECTION AND
 RISE VERTICALLY TO A POINT 6? ABOVE THE FICTURE RIM OR
 TRAP BEFORE OFFSETTING HORIZONTALLY. SEE REDLINED
 COMMENT ON SANITARY RISER DIAGRAM.
  