Plan Review Notes
Plan Review Notes For Permit 19060556
Permit Number 19060556
Review Stop E
Sequence Number 2
Notes
Date Text
2019-11-04 13:11:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 3/0 WIRE FEEDING A 350 AMP
 SERVICE. THIS WIRE IS NOT RATED FOR 350 AMP SERVICE.
 PROVIDE CORRECTION. NEC 310.15(B)(7); FBC RE E3603.1
 2. ON RISER DIAGRAM, WIRE FROM MAIN DISCONNECT TO
 INTERIOR PANELS SHOULD INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6
 3. UNDER THE TITLE FOR NEW ELECTRIC ONLY, AFCI
 PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 4. UNDER THE TITLE FOR NEW ELECTRIC ONLY AND NOTE 14,
 NOTE STATES THAT RECEPTACLES SHALL BE TAMPER RESISTANT
 PER NEC 406.11. THIS CODE SECTION DOES NOT APPLY TO
 TAMPER RESISTANT RECEPTACLES. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 NEC 220; FBC RE E3602.2
 6. IT APPEARS THIS PANEL IS LOCATED IN A SEPARATE
 STRUCTURE FROM THE BUILDING THAT HAS THE MAIN SERVICE.
 IF THIS IS THE CASE, PANEL B WILL NEED TO EITHER HAVE A
 MAIN BREAKER, OR A DISCONNECT AHEAD OF IT AT THE
 STRUCTURE. PROVIDE CORRECTION. NEC 225.31, 225.32
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  