2019-06-20 15:25:51PLUMBING 1ST REVIEW**DENIED**
  
 1) PLAN SHOW ELC TANKLESS WATER HEATER OUTSIDE. PROVIDE
 COMPLETED INSTALLATION MANUAL WITH HEAT RISE CHARTS TO
 VERIFY SIZING AND APPROVED FOR OUTDOOR USE. FBC
 107.2.1, FBC P502.1
  
 2) THE WASHING MACHINE IS NOT SHOWN ON THE ISOMETRIC AS
 VENTED AND BRANCH LINE AS 2". FBC 406.2 REQUIRES THE
 BRANCH OR STACK TO BE MIN 3" AND BE VENTED FBC P901.2.1
  
 3) THE WET BAR AND WASHINE MACHINE ARE ON SEPERATE
 BUILDING DRAINS WHICH BOTH WILL REQUIRE A VENT THAT
 EXTENDS TO THE OUTDOORS. AAV IS NOT PERMITTED. FBC P
 904.1
  
 4) PROVIDE SHOWER PAN/RECESS DETAIL. SHOW MATERIAL USED
 AND THAT FLOOR WILL BE PRE-PITCHED @2%. FBC 107.2.1
  
 5) ALL SHEETS SIGNED BY SANDRA PUERTA ARC #95385 ARE
 COPIES. FS 481 REQUIRES EACH PAGE TO BE WET SIGNED.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  