| Plan Review Notes For Permit 19060556 |
| Permit Number |
19060556 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-20 15:25:51 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PLAN SHOW ELC TANKLESS WATER HEATER OUTSIDE. PROVIDE | | | COMPLETED INSTALLATION MANUAL WITH HEAT RISE CHARTS TO | | | VERIFY SIZING AND APPROVED FOR OUTDOOR USE. FBC | | | 107.2.1, FBC P502.1 | | | | | | 2) THE WASHING MACHINE IS NOT SHOWN ON THE ISOMETRIC AS | | | VENTED AND BRANCH LINE AS 2". FBC 406.2 REQUIRES THE | | | BRANCH OR STACK TO BE MIN 3" AND BE VENTED FBC P901.2.1 | | | | | | 3) THE WET BAR AND WASHINE MACHINE ARE ON SEPERATE | | | BUILDING DRAINS WHICH BOTH WILL REQUIRE A VENT THAT | | | EXTENDS TO THE OUTDOORS. AAV IS NOT PERMITTED. FBC P | | | 904.1 | | | | | | 4) PROVIDE SHOWER PAN/RECESS DETAIL. SHOW MATERIAL USED | | | AND THAT FLOOR WILL BE PRE-PITCHED @2%. FBC 107.2.1 | | | | | | 5) ALL SHEETS SIGNED BY SANDRA PUERTA ARC #95385 ARE | | | COPIES. FS 481 REQUIRES EACH PAGE TO BE WET SIGNED. | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | |
|