| Plan Review Notes For Permit 19060556 |
| Permit Number |
19060556 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-10 13:38:11 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PAGE E-1 | | | | | | 1) PANEL SCHEDULE SHOWS #14 WIRE ON 20A BREAKERS | | | | | | 2) RISER SHOWS NEW 150A MAIN DISCONNECT THIS NEEDS TO | | | BE GROUPED WITH THE 200A MAIN. | | | NOT SURE IF IT IS??? | | | | | | 3) NEED AN OUTLET AT THE FRONT OF THE BUILDING |
|