| 2019-06-17 13:37:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE LETTER NARRATIVE INDICATES FBC REFERENCES. |
| | |
| | PER THE FLORIDA FIRE PREVENTION CODE OCCUPANCY |
| | CLASSIFICATION AND SEPARATION IS ADDRESSED WITHIN |
| | CHAPTER 6 |
| | |
| | PER NFPA 101, CH 6 |
| | |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR |
| | STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL |
| | BE CLASSIFIED IN |
| | ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY |
| | CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| | JURISDICTION WHERE THERE IS A |
| | QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL |
| | CASE. |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO |
| | OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE |
| | OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE |
| | OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| | ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | THE TABLE INDICATES A 2 HR RATING BETWEEN STORAGE/ |
| | BUSINESS & MERCANTILE. A REDUCTION OF 1HR FOR FIRE |
| | SPRINKLER PROTECTION. |
| | |
| | |
| | BASED ON THE REVIEW TO ELIMINATE THE EXISITNG 1 HR |
| | RATING AND REVIEW OF THE ABOVE FFPC REFERENCES THE |
| | REQUEST IS NOT APPROVED. |
| | |
| | |
| | PLEASE REVIEW THE ABOVE AND PROVIDE ADDITIONAL |
| | INFORMATION AND APPLICABLE CODE REFERENCES FOR REVIEW. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |