Plan Review Notes
Plan Review Notes For Permit 19060531
Permit Number 19060531
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-25 12:02:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF WORK ON
 WALLS(WALLPAPER/MOLDINGS) AND CEILINGS; HOWEVER, NO
 INDICATIONS OF FIRE ALARM AND/OR FIRE SPRINKLER DEVICES
 OR FUNCTIONS.
  
 THE FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE
 MAINTAINED THROUGHOUT CONSTRUCTION.
  
 ANY WORK ON THE FIRE ALARM OR SPRINKLERS SYSTEM SHALL
 BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE TO THE ABOVE COMMENTS.
  
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
  