Plan Review Notes
Plan Review Notes For Permit 19060516
Permit Number 19060516
Review Stop E
Sequence Number 2
Notes
Date Text
2019-06-18 06:52:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE AND SEAL.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 (SEE SIGNATURE REVIEW FOR MORE INFORMATION.)
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NO VALUE STATED ON CONTRACT PROVIDED. MUST
 INCLUDE ALL MATERIALS, EVEN IF THEY ARE TO BE INSTALLED
 OR FURNISHED BY OTHERS.)
 3. PROVIDE SPEC SHEETS FOR CAMERAS TO CONFIRM LISTING.
 NEC 110.3 (NOT PROVIDED. REQUIRED EVEN IF INSTALLED BY
 OTHERS. IF A SUB-CONTRACTOR IS PULLING A SUB-PERMIT
 UNDER THIS PERMIT, THEY CAN SUBMIT THE SPEC SHEETS. SOW
 STATES THE CONTRACTOR OR A CONTRACTOR SECURITY VENDOR
 WILL INSTALL ALL FIELD DEVICES WHICH CONFLICTS WITH THE
 STATEMENT AT THE TOP OF THE SOW THAT STATES CONTRACTOR
 WILL NOT INSTALL FIELD DEVICES. WHICH IS IT? CLARIFY
 AND/OR CORRECT AS NECESSARY. WPB FBC 107.2.1)
  
 NEW COMMENT:
  
 4. IF THERE IS TO BE ACCESS CONTROL AS PART OF THIS
 PLAN, FIRE DEPARTMENT WILL ALSO HAVE TO REVIEW. PLEASE
 CLARIFY. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  