| 2019-06-18 06:52:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. THIS PERSON MUST BE A LICENSED DESIGN |
| | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. A |
| | DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE AND SEAL. |
| | PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| | (SEE SIGNATURE REVIEW FOR MORE INFORMATION.) |
| | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 (NO VALUE STATED ON CONTRACT PROVIDED. MUST |
| | INCLUDE ALL MATERIALS, EVEN IF THEY ARE TO BE INSTALLED |
| | OR FURNISHED BY OTHERS.) |
| | 3. PROVIDE SPEC SHEETS FOR CAMERAS TO CONFIRM LISTING. |
| | NEC 110.3 (NOT PROVIDED. REQUIRED EVEN IF INSTALLED BY |
| | OTHERS. IF A SUB-CONTRACTOR IS PULLING A SUB-PERMIT |
| | UNDER THIS PERMIT, THEY CAN SUBMIT THE SPEC SHEETS. SOW |
| | STATES THE CONTRACTOR OR A CONTRACTOR SECURITY VENDOR |
| | WILL INSTALL ALL FIELD DEVICES WHICH CONFLICTS WITH THE |
| | STATEMENT AT THE TOP OF THE SOW THAT STATES CONTRACTOR |
| | WILL NOT INSTALL FIELD DEVICES. WHICH IS IT? CLARIFY |
| | AND/OR CORRECT AS NECESSARY. WPB FBC 107.2.1) |
| | |
| | NEW COMMENT: |
| | |
| | 4. IF THERE IS TO BE ACCESS CONTROL AS PART OF THIS |
| | PLAN, FIRE DEPARTMENT WILL ALSO HAVE TO REVIEW. PLEASE |
| | CLARIFY. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |