Plan Review Notes
Plan Review Notes For Permit 19060508
Permit Number 19060508
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-14 09:59:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, THE ASSEMBLY W-M-13 PROPOSED HAS A
 DESIGN PRESURE LIMITATION OF -80. SEE PAGE S0.1, DESIGN
 PRESSURE REQUIREMENTS FOR THIS ROOF ARE:
  
 ZONE 2 -65.8
 ZONE 3 -99.1
  
 SEE LIMITATION #7, ENHANCED FASTENING SHALL BE
 CALCULATED BY A QUALIFIED DESIGN PROFESSIONAL
 (ENGINEERING REQUIRED).
  
  