| Plan Review Notes For Permit 19060393 |
| Permit Number |
19060393 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-24 11:38:10 | PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE | | | REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL | | | PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE | | | RE-REVIEW OF SUBMITTED CORRECTIONS | | | | | | 1) SHT. P 4.1 CALLS OUT THE WATER HEATER AS .93 E.F BUT | | | THE R405-2017 FORM CALLS OUT .96 EF. PLEASE CLARIFY AND | | | PROVIDE INSTALLATION MANUAL AS MODEL NUMBER YOU PROVIDE | | | IS NOT VALID. FBC 107.2.1 | | | | | | 2) PROVIDE AN EXISTING FLOOR PLAN. FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|