Plan Review Notes
Plan Review Notes For Permit 19060393
Permit Number 19060393
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-05 14:32:57BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE TWO COPIES OF A CURRENT SURVEY.
 107.2.5
  
 2. PALM BEACH COUNTY IMPACT FEES MAY APPLY.
 PLEASE PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE
 FORM TO THE PBC IMPACT FEE OFFICE. THE FORM CAN BE
 FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION
 /PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 3. ROOFING PRODUCT APPROVALS REQUIRED.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 4. ROOF SHEATHING SHALL BE FASTENED WITH RING SHANK
 NAILS.
 107.2.5
  
 5. DESIGN PROFESSIONAL SHALL STATE ON PLAN TYPE AND R
 VALUE OF INSULATION TO BE INSTALLED.
 ENERGY SUBMITTAL INDICATES INSULATION SHALL BE BLOWN
 IN. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 THIS TYPE OF INSULATION.
  
 6. PROVIDE DESIGN PRESSURES FOR ALL WINDOW AND EXT.
 DOOR OPENINGS. YOU MAY PLACE THESE VALUES ON WINDOW AND
 DOOR SCHEDULE OR PLACE THEM ON THE PLAN NEXT TO EACH
 OPENING.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 7. PROVIDE FRAMING DETAIL FOR REAR AWNING. INCLUDE SITE
 SPECIFIC ENGINEERING SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL.
 107.2.5
  
 8. PLAN PAGE A-001 UTILIZES BOTH NGVD AND NAVD VERTICAL
 DATUM. CONVERT ALL NGVD DATUM TO NAVD88.
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM.
  
 9. PROVIDE SHOP DRAWINGS FOR PROPOSED PRE-ENGINEERED
 ALUMINUM TRELLIS. DESIGNER TO REVIEW AND APPROVE..
 FBC 107.3.4 RULE 9N-3 REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD.
  
 10. PROVIDE PRODUCT APPROVALS FOR LINTEL L1.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE LINTEL SUBMITTALS.
  
 11. PROVIDE CONNECTION DETAIL FOR PROPOSED CMU WALL TO
 EXISTING STRUCTURE.
 107.2.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  