Plan Review Notes
Plan Review Notes For Permit 19060381
Permit Number 19060381
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-17 13:22:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.0 - THERE IS NO WIDTH DIMENSION INDICATED.
  
 PER NFPA 101 - CH 7 MEANS OF EGRESS
  
  
 7.2.2.2.1.2* MINIMUM NEW STAIR WIDTH. (SEE ALSO 7.3.3.)
 (A) WHERE THE TOTAL OCCUPANT LOAD OF ALL STORIES SERVED
 BY THE STAIR
 IS FEWER THAN 50, THE MINIMUM WIDTH CLEAR OF ALL
 OBSTRUCTIONS,
 EXCEPT PROJECTIONS NOT MORE THAN 4? IN. (114 MM) AT OR
 BELOW
 HANDRAIL HEIGHT ON EACH SIDE, SHALL BE 36 IN. (915 MM).
  
 PLEASE PROVIDE.
  
  
  
 2) THERE ARE NO INDICATIONS OF WHAT THE EXISTING STAIR
 LAYOUT WAS. IS IT THE SAME?
  
 PLEASE PROVIDE A DESIGN/DRAWING OF THE EXISTING STAIR.
  
  
  
 3) SHEET A 1.0 - THERE ARE NO INDICATIONS OF THE
 LANDING DIMESIONS NOR EXIT DOOR SWING AT THE TOP.
  
 7.2.2.3.2 LANDINGS.
 7.2.2.3.2.1 STAIRS SHALL HAVE LANDINGS AT DOOR
 OPENINGS, EXCEPT AS
 PERMITTED IN 7.2.2.3.2.5.
 7.2.2.3.2.2 STAIRS AND INTERMEDIATE LANDINGS SHALL
 CONTINUE WITH NO
 DECREASE IN WIDTH ALONG THE DIRECTION OF EGRESS TRAVEL.
 7.2.2.3.2.3 IN NEW BUILDINGS, EVERY LANDING SHALL HAVE
 A DIMENSION,
 MEASURED IN THE DIRECTION OF TRAVEL, THAT IS NOT LESS
 THAN THE WIDTH OF THE
 STAIR.
 7.2.2.3.2.4 LANDINGS SHALL NOT BE REQUIRED TO EXCEED 48
 IN. (1220 MM) IN
 THE DIRECTION OF TRAVEL, PROVIDED THAT THE STAIR HAS A
 STRAIGHT RUN.
 7.2.2.3.2.5 IN EXISTING BUILDINGS, A DOOR ASSEMBLY AT
 THE TOP OF A STAIR
 SHALL BE PERMITTED TO OPEN DIRECTLY TO THE STAIR,
 PROVIDED THAT THE DOOR
 LEAF DOES NOT SWING OVER THE STAIR AND THE DOOR OPENING
 SERVES AN AREA
 WITH AN OCCUPANT LOAD OF FEWER THAN 50 PERSONS.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE.
  
  
 4) SHEET A 2.0 - CALL-OUTS # 2 & 3 INDICATED A HANDRAIL
 HEIGHT OF 2'11"; CALL-OUT # 5 INDICATES 2'11". WHICH
 ONE IS CORRECT.
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  