| Date |
Text |
| 2019-08-20 11:54:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54= STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | 1. SECOND REQUEST; PER FBC PL 608.1, SPECIFY AND |
| | PROVIDE BACKFLOW PREVENTION DEVICE IN THE WATER SERVICE |
| | DOWNSTREAM OF WATER METER. IT IS THE POSITION OF THIS |
| | OFFICE, THAT EACH INDIVIDUAL UNIT IS A SEPARATE ENTITY |
| | AND IS REQUIRED TO PROVIDE PROTECTION TO THE BUILDING |
| | POTABLE WATER SYSTEM FROM POTENTIAL CROSS CONNECTIONS |
| | THAT MAY ARISE IN A GIVEN UNIT. PLEASE CONTACT MR. TIM |
| | LARGE, CHIEF PLUMBING INSPECTOR AT 561-805-6692 IF |
| | ADDITIONAL CLARIFICATION IS REQUIRED. |
| | 2. ADDITIONAL CLARIFICATION REQUIRED; PROVIDE NOTE ON |
| | PLAN SHEET P-100: PROVIDE TRAP PRIMERS AT ALL FLOOR |
| | DRAINS. SEE TRAP PRIMER DETAIL ON P-501. |
| | 3. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A |
| | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY |
| | VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR |
| | ENGINEERS. ADDITIONALLY, THE DIGITAL SIGNATURE MUST |
| | INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC |
| | 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS |
| | 471/481 (NO DIGITAL SIGNATURE ON PLANS SUBMITTED.) |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19060311 701 S ROSEMARY AVE # 140 |
| | |