| Plan Review Notes For Permit 19060311 |
| Permit Number |
19060311 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-03 11:50:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) DOOR 104 IS AN EXIT DOOR AND THE HARDWARE WITHIN THE | | | DOOR SCHEDULE INDICATES IT WILL HAVE KEYED ENTRY. | | | | | | THE HARDWARE SHALL COMPLY WITH NFPA 101 CH 7, MEANS OF | | | EGRESS. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM | | | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR | | | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO | | | ELEVATED | | | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON | | | LABORATORY | | | FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS | | | SIDE. | | | | | | | | | PLEASE ENSURE COMPLIANCE FOR FIRE INSPECTIONS. | | | | | | | | | | | | 2) ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE | | | PERMIT AND SHOP DRAWINGS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|