Plan Review Notes
Plan Review Notes For Permit 19060282
Permit Number 19060282
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-18 15:11:22PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE
 REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE
 RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) THE CAPPING OF THE EXISTING SHOWER DRAIN AND THE
 RELOCATING OF THE TUB DRAIN TO CENTER ON THE NEW SHOWER
 OPENING WILL REQUIRE A FIRE STOPPING DETAIL. SHOW HOW
 YOU INTEND ON MAINTAINING THE EXISTING FIRE RATING AND
 REPAIR ANY HOLES IN FLOORING. FBC 107.2.1
  
 2) PROVIDE SHOWER PAN DETAIL. SHOW MATERIAL BEING USED
 AND THAT THE FLOOR WILL BE PRE-PITCHED MIN 2%., FBC
 107.3.5, FBC P417.5.2
  
 3) ADD NOTE TO PLAN OR PROVIDE SHOWER VALVE MANUAL
 SHOWING PRESSURE BALANCE AND APPROVED ASSE 1016.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  