Plan Review Notes
Plan Review Notes For Permit 19060282
Permit Number 19060282
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-17 13:35:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060282
 ADD: 1701 S. FLAGLER DR. SUITE: 1001
 CONT: CURTIS MEADE INC.
 TEL: 561-742-1140 X 3
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 17, 2019
 ACTION: DENIED
  
 1) THE CONTRACTORS PLAN FAILS TO INDICATE HOW
 COMPLIANCE WITH 2509.2 OF THE 2017 FBC-B. THE BASE
 REQUIRED FOR TILE WALLS IN SHOWERS SHALL COMPLY WITH
 THE 2017 FBC-B SECTION:
  
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURER'S
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840.
  
 TABLE 2509.2 / BACKERBOARD MATERIALS
  
 MATERIAL-----------------------------------------------
 ------------ STANDARD
  
 GLASS MAT GYPSUM BACKING PANEL
 ---------------------------ASTM C1178
  
 NONASBESTOS FIBER-CEMENT BACKER BOARD---------ASTM
 C1288 OR ISO 8336,
 CATEGORY C
  
 NONASBESTOS FIBER-MAT REINFORCED
 ------------------------ASTM 1325
 CEMENTITIOUS BACKER UNIT
 PLEASE INDICATE WHICH MATERIAL IS GOING TO BE USED FOR
 THE TILE BASE IN THE SHOWER.
  
 2) THE PLANS ARE NOT CLEAR IF THE UNIT BEING REMODELED
 IS ON THE 1ST FLOOR OR THE 10TH FLOOR. UNITS ON THE 1ST
 FLOOR DOES NOT REQUIRE FLOOR UNDERLAYMENT FOR SOUND
 PROOFING. ON FLOORS ABOVE THE 1ST FLOOR LEVEL THE
 FLOORS REQUIRE FLOOR INSULATION. THE OTHER ISSUE IS THE
 PLANS ARE NOT CLEAR IF ONLY THE CLOSET FLOOR IS BEING
 REPLACED OR IF THE WHOLE BATHROOM FLOOR IS BEING
 REPLACED.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved