| Date |
Text |
| 2019-08-01 16:13:36 | FAILED |
| | |
| | PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| | |
| | 1) REPEAT COMMENT: THE CITYPLACE RETAIL MANAGEMENT |
| | APPROVAL WAS NOT PROVIDED. EITHER PROVIDE STAMPED PLANS |
| | OR A LETTER CITING THE PLANS THAT CITYPLACE RETAIL |
| | MANAGEMENT IS APPROVING. --- THE RESPONSE STATED THAT |
| | THE APPROVAL LETTER WAS INCLUDED WITH THE RESUBMITTAL, |
| | BUT STAFF WAS UNABLE TO LOCATE THE LETTER IN THE |
| | UPLOADED FILES. |
| | |
| | 2) REPEAT COMMENT: THE ROSEMARY RETAIL CORRIDOR SUBAREA |
| | REQUIRES THAT THE STOREFRONTS ALONG ROSEMARY AVENUE AND |
| | FERN STREET HAVE A MINIMUM OF 60% TRANSPARENCY. PROVIDE |
| | VERIFICATION, IN ACCORDANCE WITH SECTION 94-109 OF THE |
| | ZONING AND LAND DEVELOPMENT REGULATIONS, THAT THE |
| | MINIMUM TRANSPARENCY IS BEING PROVIDED. --- SHEET |
| | A2.0.1 STATES THAT THE TRANSPARENCY ALONG ROSEMARY |
| | AVENUE IS 61% AND THE TRANSPARENCY ALONG FERN STREET IS |
| | 60%. PROVIDE THE LINEAR FEET OF FRONTAGE OF THE BAY FOR |
| | EACH STREET FRONT AND THE DIMENSIONS AND SQUARE FOOTAGE |
| | OF EACH GLAZED OPENING (EXISTING AND PROPOSED) ALONG |
| | BOTH STREET FRONTAGES SO THAT ZONING STAFF CAN VERIFY |
| | YOUR GLAZING PERCENTAGES. |
| | |
| | A. THE TABLE PROVIDED FOR THE ROSEMARY AVENUE FRONTAGE |
| | LOOKS TO HAVE TRANSPOSED THE MEASUREMENT VALUES. |
| | B. THE SCOPE OF WORK INCLUDES THE ENTIRE FORMER |
| | REVOLUTIONS SPACE; THEREFORE THE ENTIRE ROSEMARY |
| | FRONTAGE MUST BE USED TO VERIFY COMPLIANCE WITH THE 60% |
| | GLAZING REQUIREMENT. |
| | C. STAFF?S ROUGH CALCULATIONS DO NOT VERIFY THAT FERN |
| | STREET HAS 60% GLAZING. |
| | D. THE TABLE PROVIDED FOR THE FERN STREET FRONTAGE |
| | LISTS DIFFERENT NUMBERS IN THE MEASUREMENT VALUES THAN |
| | IT DOES IN THE CALCULATION LINE. |
| | |
| | 3) PROVIDE VERIFICATION THAT THE NEW EXTERIOR LIGHTS |
| | COMPLY WITH THE LIGHTING REQUIREMENTS OF SECTION |
| | 94-113(B) OF THE ZONING AND LAND DEVELOPMENT |
| | REGULATIONS. --- THE NOTATION THAT WAS ADDED REGARDING |
| | THE LIGHTING LEVELS NEEDS TO BE INCLUDED ON THE SIGNED |
| | AND SEALED DRAWINGS DONE BY THE LIGHTING ENGINEER NOT |
| | ON THE ARCHITECTURAL PLANS. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
| | [email protected] |
| | |