| 2019-07-16 12:31:05 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19060241 |
| | 7/16/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.2: PROVIDE AC COOLING AND HEATING |
| | CALCULATIONS FOR THE NEW FCU'S IN ACCORDANCE WITH |
| | SECTION C403.2.1 FBC EC AND SECTION 312.1 FBC M. |
| | |
| | 2) M1.2: REFER TO SECTION 809.2 FBC-17 EXISTING |
| | BUILDING CODE AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE |
| | 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. |
| | |
| | 3) M1.2: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW |
| | FCU'S- SECTION 307.2.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |